Posts Tagged ‘vent controlled fire’

Homewood, IL LODD: Part 2

Sunday, November 21st, 2010

This post continues examination of the incident that took the life of Firefighter Brian Carey and seriously injured Firefighter Kara Kopas on the evening of March 30, 2010  while they were operating a hoseline in support of primary search in a small, one-story, wood frame dwelling with an attached garage at 17622 Lincoln Avenue in Homewood, Illinois.

This post focuses on firefighting operations, key fire behavior indicators, and firefighter rescue operations implemented after rapid fire progression that trapped Firefighters Carey and Kopas.

Firefighting Operations

After making initial assignments, the Incident Commander performed reconnaissance along Side Bravo to assess fire conditions. Fire conditions at around the time the Incident Commander performed this reconnaissance are illustrated in Figure 7. After completing recon of Side B, the Incident Commander returned to a fixed command position in the cab of E-534 (in order to monitor multiple radio frequencies).

Figure 7. Conditions Viewed from Side C during the Incident Commander’s Recon

Note: John Ratko Photo from NIOSH Death in the Line of Duty Report F2010-10.

Engine 1340 (E-1340) arrived and reported to Command for assignment. The five member crew of this company was split to assist T-1220 with vertical ventilation, horizontally ventilate through windows on Sides B and D, and to protect Exposures D and D2.

One member of E-1340 assisted T-1220 and the remaining members vented the kitchen windows on SidesD and B, while the E-1340 Officer stretched a 1-3/4” (45 mm) hoseline from E-534 to protect exposures on Side D. However, this line was not charged until signficantly later in the incident (see Figure 14). Figure 8 (a-c) illustrates changing conditions as horizontal ventilation is completed on Sides B and D.

Figure 8. Sequence of Changing Conditions Viewed from the A/B Corner

At 2105 Command reported that crews were conducting primary search and were beginning to vent.

Note the B-SAHF indicators visible from the A/B Corner in Figure 8a: Dark gray smoke from the door on Side A with the neutral plane at approximately 18” (0.25 m) above the floor. Velocity and turbulence are moderate and a bidirectional air track is evident at the doorway.

As the 2-1/2” (64 mm) handline reached the kitchen, flames were beginning to breach the openings in the Side C wall of the house and thick black smoke had banked down almost to floor level. As noted in Figure 3 (and subsequent floor plan illustrations), there were doors and windows between the house and addition in the Utility Room and Bedroom 2 . The Firefighter from E-534 had a problem with his protective hood and handed the nozzle off to Firefighter Carey and instructed him to open and close the bail of the nozzle quickly. After doing so, the Firefighter from E-534 retreated along the hoseline to the door on Side A to correct this problem (he is visible in the doorway in Figure 8c).

As E-1340 vents windows on Sides B (see Figure 8b) and D, the level of the neutral plane at the doorway on Side A lifts, but velocity and turbulence of smoke discharge increases. Work continues on establishing a vertical vent, but is hampered by smoke discharge from the door on Side A.

After horizontal ventilation of Sides B and D, velocity and turbulence of smoke discharge continues to increase and level of the upper layer drops to the floor as evidenced by the neutral plane at the door on Side A (see Figures 8b and 8c)

The photo in Figure 8c was taken just prior to the rapid fire progression that trapped Firefighters Carey & Kopas. The Firefighter from E-534 is visible in the doorway correcting a malfunction with his protective hood.

As T-1220B reached the hallway leading to the bedrroms, they felt a significant increase in temperature and visibility worsened. After searching Bedroom 2 and entering Bedroom 1 temperature contiued to increase and T-1220B observed flames rolling through the upper layer in the hallway leading from Bedroom 2 and the Bathroom. Note: NIOSH Death in the Line of Duty Report 2010-10 does not specify if T-1220B searched Bedroom 2, but this would be consistent with a left hand search pattern. They immedidately retreated to the Living Room looking for the hoseline leading to the door on Side A. As they did so, they yelled to the crew on the 2-1/2” (64 mm) handline to get out.

Extreme Fire Behavior

Firefighter Kopas felt a rapid increase in temperature as the upper layer ignited throughout the living room and the fire in this compartment transitioned to a fully developed stage. She yelled to Firefighter Carey, but received no response as she turned to follow the 2-1/2” (64 mm) hoseline back to the door on Side A. She made it to within approximately 4’ (1.2 m) of the front door when her protective clothing began to stick to melted carpet and she became stuck. T-1220B saw that she was trapped, reentered and pulled her out.

Figure 12. Position of the Crews as the Extreme Fire Behavior Phenomena Occurred

Note: It is unknown if T-1220B searched Bedroom 2 before entering Bedroom 1. However, this would be consistent with a left hand search pattern.

Figure 13. Conditions Viewed from the Alpha/Bravo Corner as the Extreme Fire Behavior Occured

Note: Warren Skalski Photo from NIOSH Death in the Line of Duty Report F2010-10.

Figure 14. Conditions Viewed from the Alpha/Delta Corner as the Extreme Fire Behavior Occured

Note: Warren Skalski Photo from NIOSH Death in the Line of Duty Report F2010-10.

Following the transition to fully developed fire conditions in the living room, the Incident Commander ordered T-1220 off the roof. As illustrated in Figure 14, the exposure protection line stretched by E-1340 was not charged until after Firefighter Carey was removed from the building.

Figure 15. Position of Search and Fire Control Crews after Rapid Fire Progress

Firefighter Rescue Operations

The Incident Commander and Firefighter from E-534 (who had retreated to the door due to a problem with his protective hood), pulled a second 1-3/4” (45 mm) line from E-534. T-1220B re-entered the house with this hoseline to locate Firefighter Carey.

While advancing into the living room, T-1220B discovered that E-534’s 2-1/2” (64 mm) handline. They controlled the fire in the living room using a direct attack on burning contents and advanced to the kitchen where they discovered Firefighter Carey entangled in the 2-1/2” (64 mm) handline. Firefighter Carey’s helmet and breathing apparatus facepiece were not in place.

T-1220B removed Firefighter Carey from the building where he received medical care from T-1145. A short time later, Firefighter Carey became apenic and pulseless. After the arrival of Ambulance 2101 (A-2101), Firefighter Carey was transported to Advocate South Suburban Hospital in Hazel Crest, IL where he was declared dead at 10:03 pm.

According to the autopsy report, Firefighter Carey had a carboxyhemoglobin (COHb) of 30% died from carbon monoxide poisoning. The NIOSH Death in the Line of Duty Report (2010) did not indicate if the medical examiner tested for the presence of hydrogen cyanide (HCN) or if thermal injuries were a contributing factor to Firefighter Carey’s death.

Timeline

Review the Homewood, Illinois Timeline (PDF format) to gain perspective of sequence and the relationship between tactical operations and fire behavior.

Contributing Factors

Firefighter injuries often result from a number of causal and contributing factors. NIOSH Report F2010-10 identified the following contributing factors in this incident that led to the death of Firefighter Brian Carey and serious injuries to Firefighter Kara Kopas.

  • Well involved fire with trapped civilian upon arrival.
  • Incomplete 360o situational size-up
  • Inadequate risk-versus-gain analysis
  • Ineffective fire control tactics
  • Failure to recognize, understand, and react to deteriorating conditions
  • Uncoordinated ventilation and its effect on fire behavior
  • Removal of self-contained breathing apparatus (SCBA) facepiece
  • Inadequate command, control, and accountability
  • Insufficient staffing

Questions

The following questions focus on fire behavior, influence of tactical operations, and related factors involved in this incident.

  1. What type of extreme fire behavior phenomena occurred in this incident? Why do you think that this is the case (justify your answer)?
  2. How did the conditions necessary for this extreme fire behavior event develop (address both the fuel and ventilation sides of the equation)?
  3. What fire behavior indicators were present in the eight minutes between arrival of the first units and occurrence of the extreme fire behavior phenomena (organize your answer using Building, Smoke, Air Track, Heat, and Flame (B-SAHF) categories)? In particular, what changes in fire behavior indicators would have provided warning of impending rapid fire progression?
  4. Did any of these indicators point to the potential for extreme fire behavior? If so, how? If not, how could the firefighters and officers operating at this incident have anticipated this potential?
  5. What was the initiating event(s) that lead to the occurrence of the extreme fire behavior that killed Firefighter Carey and injured Firefighter Kopas?
  6. How did building design and construction impact on fire behavior and tactical operations during this incident?
  7. What action could have been taken to reduce the potential for extreme fire behavior and maintain tenable conditions during primary search operations?
  8. How would you change, expand, or refine the list of contributing factors identified by the NIOSH investigators?

Homewood, IL LODD

Saturday, November 13th, 2010

Introduction

While formal learning is an essential part of firefighters’ and fire officers’ professional development, informal learning is equally important, with lessons frequently shared through the use of stores. Stories are about sharing knowledge, not simply about entertainment. It is their ability to share culture, values, vision and ideas that make them so critical. They can be one of the most powerful learning tools available (Ives, 2004). “Only by wrestling with the conditions of the problem at hand and finding his own way out, does [the student] think” (Dewey, 1910, p. 188).

Developing mastery of the craft of firefighting requires experience. However, it is unlikely that we will develop the base of knowledge required simply by responding to incidents. Case studies provide an effective means to build our knowledge base using incidents experienced by others. This case is particularly significant as the circumstances could be encountered by almost any firefighter.

Aim

Firefighters and fire officers recognize and respond appropriately to the hazards of ventilation controlled fires in small, Type V (wood frame), single family dwellings.

References

National Institute for Occupationsl Safey and Health (NIOSH). (2010). Death in the line of duty: Report F2010-10. Retrieved October 22, 2010 from http://www.cdc.gov/niosh/fire/pdfs/face201010.pdf.

Ives, B. (2004) Storytelling and Knowledge Management: Part 2 – The Power of Stories. Retrieved May 6, 2010 from http://billives.typepad.com/portals_and_km/2004/08/storytelling_an_1.html

Dewey, J. (1910) Democracy and education. New York: McMillan

Learning Activity

Review the incident information and discuss the questions provided. Focus your efforts on understanding the interrelated impact of ventilation and fire control tactics on fire behavior. Even more important than understanding what happened in this incident is the ability to apply this knowledge in your own tactical decision-making.

The Case

This case study was developed using NIOSH Death in the Line of Duty: Report F2010-10 (NIOSH, 2010).

On the evening of March 30, 2010, while operating at a fire in a small single family dwelling, Firefighter/Paramedic Brian Carey and Firefighter/Paramedic Kara Kopas were assigned to assist in advancement of a 2-1/2” handline for offensive fire attack and to support primary search. Shortly after entering the building conditions deteriorated and they were trapped by rapid fire progression. Firefighter Kopas suffered 2nd and 3rd degree burns to her lower back, buttocks, and right wrist. Firefighter Carey died from carbon monoxide poisoning and inhalation of smoke and soot. A 84 year old male civilian occupant also perished in the fire.

Figure 1. Side A Post Fire

Side A Post Fire

Note: National Institute for Occupational Safety and Health (NIOSH)

Building Information

This incident involved a 950 ft2 (88.26 m2), one-story, single family dwelling constructed in 1951. The house was of Type V (wood frame) construction with a hip roof covered with asphalt shingles. The roofline of the hip roof provided a small attic space. Sometime after the home was originally constructed an addition C was built that attached the house to a garage located on Side C. Compartment linings were drywall. The house, garage, and addition were all constructed on a concrete slab.

There were several openings between the house and addition, including two doors, and two windows (see Figure 3).

Note: The number and nature of openings between the garage and addition is not reported, but likely included a door and possibly a window (given typical garage construction). NIOSH investigators did not determine if the doors and windows between the house, addition, and garage were open or closed at the time of the fire as they were consumed by the fire and NIOSH did not interview the surviving occupant (S. Wertman, personal communication, November 17, 2010). The existence and position of the door shown in the wall between the addition and garage is speculative (based on typical design features of this type of structure).

Figure 2. Plot Plan and Apparatus Positioning

Figure 3. Floor Plan 17622 Lincoln Avenue

The Fire

Investigators believe that the fire originated in an addition that was constructed between the original home and the two-car garage. The surviving occupant reported that she observed black smoke and flames from underneath the chair that her disabled husband was sitting in.

The addition was furnished as a family room and fuel packages included upholstered furniture and polyurethane padding. The civilian victim also had three medical oxygen bottles (one D Cylinder (425 L) and two M-Cylinders (34 L). It is not know if the oxygen in these cylinders was a factor in fire development. The garage contained a single motor vehicle in the garage and other combustible materials.

After calling 911 and attempting to extinguish the fire, the female occupant exited the building. NIOSH Death in the Line of Duty Report 2010-10 did not specify this occupants egress path or if she left the door through which she exited open or closed (NIOSH did not interview the occupant, she was interviewed by local fire and law enforcement authorities). The NIOSH investigator (personal communications S. Wertman, November 17, 2010) indicated that the occupant likely exited through the exterior door in the addition or through the door on Side A. Give rapid development through flashover in the addition, it is likely that the exterior door in the addition or door to the garage was open, pointing to the likelihood that the occupant exited through this door. Subsequent rapid extension to the garage was likely based on design features of the addition and garage or some type of opening between these two compartments. As similar extension did not occur in the house, it is likely that the door and windows in the Side C wall of the house were closed.

In the four minutes between when the incident was reported (20:55 hours) and arrival of a law enforcement unit (20:59), the fire in the addition had progressed from the incipient stage to fully developed fire conditions in both the addition and garage.

Dispatch Information

At 2055 hours on March 30, 2010, dispatch received a call from a resident at 17622 Lincoln Avenue stating that her paralyzed husband’s chair was on fire and that he was on oxygen. The first alarm assignment consisting of two engines, two trucks, a squad, and ambulance, and fire chief was dispatched at 2057.

Table 1. On-Duty and Additional Unit Staffing of First Alarm Resources

Unit

Staffing

Engine 534 Lieutenant, Firefighter, Engineer
Ambulance 564 2 Firefighter Paramedics
Truck 1220 (Auto Aid Department) Lieutenant, 2 Firefighters, Engineer
Engine 1340 (Auto Aid Department) Lieutenant 3 Firefighters, Engineer
Truck 1145 (Auto Aid Department) Lieutenant, 2 Firefighters, Engineer
Squad 440 (Auto Aid Department) Lieutenant, 3 Firefighters
Chief Chief

Note: This table was developed by integrating data from Death in the Line of Duty Report 2010-10 (NIOSH, 2010).

Weather Conditions

The weather was clear with a temperature of 12o C (53o F). Firefighters operating at the incident stated that wind was not a factor.

Conditions on Arrival

A law enforcement officer arrived prior to fire companies and reported that the house was “fully engulfed” and that the subject in the chair was still in the house.

Truck 1220 (T-1220) arrived at 2101, observed that the fire involved a single family dwelling, and received verbal reports from law enforcement and bystanders that the male occupant was still inside. Note: The disabled male occupant’s last known location was in the addition between the house and garage, but it is unknown if this information was clearly communicated to T-1220 or to Command (E-534 Lieutenant).

Engine 534 (E-534) arrived just behind T-1220 and reported heavy fire showing. E-534 had observed flames from Side C during their response and discussed use of a 2-1/2” (64 mm) handline for initial attack.

Firefighting Operations

Based on the report of a trapped occupant, T-1220B (Firefighter and Apparatus Operator) prepared to gain entry and conduct primary search. Note: Based on data in NIOSH Death in the Line of Duty Report 2010-10, it is not clear that this task was assigned by the initial Incident Commander (Engine 534 Lieutenant). It appears that this assignment may have been made by the T-1220 Lieutenant, or performed simply as a default truck company assignment for offensive operations at a residential fire.

Upon arrival, the E-534 Lieutenant assumed Command and transmitted a size-up report indicating heavy fire showing. The Incident Commander(E-534 Lieutenant) assisted the E-534 Firefighter with removal of the 1-3/4” (45 mm) skid load from the solid stream nozzle on the 2-1/2” (64 mm) hose load and stretching the 2-1/2” (64 mm) handline to the door on Side A. The E-534 Apparatus Operator charged the line with water from the apparatus tank and then hand stretched a 5” supply line to the hydrant at the corner of Lincoln Avenue and Hawthorne Road with the assistance of a Firefighter from T-1220.

Figure 4. Initiation of Primary Search

The Incident Commander (E-534 Lieutenant) assisted T-1220B in forcing the door on Side A. T-1220B made entry without a hoseline and began a left hand search as illustrated in Figure 4, noting that the upper layer was banked down to within approximately 3’ (0.9 m) from the floor).

Arriving immediately after E-534, the crew of A-564 donned their personal protective equipment and reported to the Incident Commander at the door on Side A, where he and the E-534 Firefighter were preparing to make entry with the 2-1/2” hoseline. The Incident Commander then assigned A-564 to work with the E-534 Firefighter to support search operations and control the fire.

T-1220 initiated roof operations and began to cut a ventilation opening on Side A near the center of the roof. Note: Based on data in NIOSH Death in the Line of Duty Report 2010-10, it is not clear that this task was assigned by the initial Incident Commander (Engine 534 Lieutenant). It appears that this assignment may have been made by the T-1220 Lieutenant, or performed simply as a default truck company assignment for offensive operations at a residential fire.

As illustrated in Figure 5, a large body of fire can be observed on Side C and a bi-directional air track is evident at the point of entry on Side A with dark gray smoke pushing from the upper level of the doorway at moderate velocity. All windows on Sides A and B were intact, with evidence of soot and/or condensed pyrolizate on the large picture window adjacent to the door on Side A.

Figure 5. Conditions Viewed from the Alpha/Bravo Corner at Approximately

Note: Warren Skalski Photo from NIOSH Death in the Line of Duty Report F2010-10.

The Firefighter from E-534 took the nozzle and assisted by Firefighters Carey and Kopas (A-564) stretched the 2-1/2” (64 mm) handline through the door on Side A and advanced approximately 12’ (3.66 m) into the kitchen. As they advanced the hoseline, they were passed by T-1220B, conducting primary search. The E-534 Firefighter, Firefighter Kopas (A-564), and T-1220B observed thick (optically dense), black smoke had dropped closer to the floor and that the temperature at floor level was increasing.

Figure 6. Primary Search and Fire Control Crews

Questions

Take a few minutes and consider the answers to the following questions. Remember that it is much easier to sort through the information presented by the incident when you are reading a blog post, than when confronted with a developing fire with persons reported!

  1. What B-SAHF (Building, Smoke, Air Track, Heat, & Flame) indicators were observed during the initial stages of this incident?
  2. What stage(s) of fire and burning regime(s) were present in the building when T-1220 and E-534 arrived? Consider potential differences in conditions in the addition, garage, kitchen, bedrooms, and living room?
  3. What would you anticipate as the likely progression of fire development over the next several minutes? Why?
  4. How might tactical operations (positively or negatively) influence fire development?

Ed Hartin, MS, EFO, MIFireE, CFO

Note: The number and nature of openings between the garage and addition is not reported, but likely included a door and possibly a window (given typical garage construction). NIOSH investigators did not determine if the doors and windows between the house, addition, and garage were open or closed at the time of the fire as they were consumed by the fire and NIOSH did not interview the surviving occupant (S. Wertman, personal communication, November 17, 2010). The existence and position of the door shown in the wall between the addition and garage is speculative (based on typical design features of this type of structure).

Hazards Above: Part 3

Sunday, July 25th, 2010

My last two posts (Hazards Above, Hazards Above: Part 2)examined a series of incidents involving firefighter injuries or near miss incidents involving fires occurring in or extending into void spaces in wood frame, residential structures. Yesterday, two members of the Bridgeport, Connecticut Fire Department lost their lives under similar circumstances.

Bridgeport, CT LODD

At 1553 hours on Saturday, July 24, 2010, the Bridgeport, Connecticut Fire Department was dispatched for a residential fire at 41 Elmwood Avenue. First arriving companies found heavy smoke from Floors 2 and 3 of a 2-1/2 story, wood frame, multi-family dwelling. Lieutenant Steven Velazquez and Firefighter Michael Baik were performing a search of the third floor when they transmitted a Mayday. Lieutenant Velazquez and Firefighter Baik were located on Floor 3 by the Rapid Intervention Team (RIT), but were not breathing and in cardiac arrest when removed from the building. CPR was initiated and they were transported to Bridgeport and St. Vincent’s Hospitals where they were pronounced dead.

More information on this tragic incident will be provided as it becomes available.

FBI and Ventilation Controlled Fires-the UL Experiments

As discussed in Hazards Above: Part 2, obvious smoke and air track indicators of a ventilation controlled fire may become diminished as the fire transitions from growth to decay stage. The decay stage ventilation controlled fire may present similar (but not identical) indicators to an incipient or early growth stage fire.

Underwriters Laboratories (UL) recently conducted a study of the effects of horizontal, natural ventilation on fires in residential structures (see Did You Ever Wonder. The results of this research will be released this fall along with a free on-line training program through UL University. During this research 15 experiments were conducted in two different residential structures. Fuel loading was consistent and the point of origin was a couch in the living room for each of the tests. The variable was the location, size, and sequence of horizontal ventilation. Interestingly, one observation remained remarkably consistent throughout the tests: Diminished smoke and air track indicators as the ventilation controlled fire transitioned from growth to decay stage. This is illustrated by a series of screen captures from video shot from Side A of the one-story structure used in these experiments.

Figure 1. Early Growth Stage

Figure 2. Growth Stage (Peak HRR Prior to Ventilation)

Figure 3. Decay Stage (Reduced HRR)

Figure 4. Conditions Immediately Following Ventilation (HRR Increasing)

Another commonality between each of the experiments was a fairly rapid and significant increase in HRR after ventilation was performed. In no case did ventilation (alone) improve conditions at any location or level inside the test buildings. Horizontal, natural ventilation (tactical or unplanned) with a delay in application of water to the seat of the fire will result in worsening conditions.

Situational Awareness

As illustrated in Figure 3, lack of obvious indicators can be deceptive. The structure used in the UL tests did not have normal window glazing as this would have resulted in less predictability in the exact location and sequence of ventilation. However, in an actual structure fire, observation of smoke conditions through windows, condensation on window glazing (incipient or early growth stage) and condensed pyrolizate (decay stage), and heat effects on window treatments (e.g., curtains, blinds) can provide important cues related to the stage of fire development and burning regime.

It is critical to take a holistic approach to observation of fire behavior indicators, to begin this process from the exterior, and to continue this process while operating on the interior.

Ed Hartin, MS, EFO, MIFIreE, CFO

Hazards Above: Part 2

Monday, July 19th, 2010

My last post, Hazards Above, provided a brief overview of three incidents involving extreme fire behavior in the attic or truss loft void spaces of wood frame dwellings. This post will examine the similarities and differences between these lessons and identify several important considerations when dealing with fires occurring in or extending to void spaces. At the conclusion of Hazards Above, I posed five questions:

  1. What is similar about these incidents and what is different?
  2. Based on the limited information currently available, what phenomena do you think occurred in each of the cases? What leads you to this conclusion?
  3. What indicators might have pointed to the potential for extreme fire behavior in each of these incidents?
  4. How might building construction have influenced fire dynamics and potential for extreme fire behavior in these incidents?
  5. What hazards are presented by fires in attics/truss lofts and what tactics may be safe and effective to mitigate those hazards?

Similarities and Differences

The most obvious similarities between these incidents was that the buildings were of wood frame construction, the fire involved or extended to an attic or truss loft void space, and that some type of extreme fire behavior occurred. In two of the incidents firefighters were seriously injured, while in the other firefighters escaped unharmed.

Given the limited information available from news reports and photos taken after the occurrence of the extreme fire behavior events, it is not possible to definitively identify what types of phenomena were involved in these three incidents. However, it is interesting to speculate and consider what conditions and phenomena could have been involved. It might be useful to examine each of these incidents individually and then to return to examine fire behavior indicators, construction, and hazards presented by these types of incidents.

Minneapolis, MN

In the Minneapolis incident the fire occurred in an older home with legacy construction and relatively small void spaces behind the knee walls and above the ceiling on Floor 3. The triggering event for the occurrence of extreme fire behavior is reported to be opening one of the knee walls on Floor 3. As illustrated in Figure 1, the fire appeared to transition quickly to a growth stage fire (evidenced by the dark smoke and bi-directional air track from the windows on Floor 3 Side A. However blast effects on the structure are not visible in the photo and were not reported.

Figure 1. Minneapolis MN Incident: Conditions on Side A

Note: Photo by Steve Skar

Potential Influencing Factors: While detail on this specific incident is limited, it is likely that the fire burning behind the knee wall was ventilation controlled and increased ventilation resulting from opening the void space resulted in an increase in heat release rate (HRR). Potential exists for any compartment fire that progresses beyond the incipient stage to become ventilation controlled. This is particularly true when the fire is burning in a void space.

Extreme Fire Behavior: While statements by the fire department indicate that opening the knee wall resulted in occurrence of flashover, this is only one possibility. As discussed in The Hazard of Ventilation Controlled Fires and Fuel and Ventilation, increasing ventilation to a ventilation controlled fire will result in increased HRR. Increased HRR can result in a backdraft (if sufficient concentration of gas phase fuel is present), a vent induced flashover, or simply fire gas ignition (such as rollover or a flash fire) without transition to a fully developed fire.

Harrisonburg, VA

The Harrisonburg incident involved extreme fire behavior in Exposure D (not the original fire unit). The extreme fire behavior occurred after members had opened the ceiling to check for extension. However, this may or may not have been the precipitating event. As illustrated in Figure 2, as members prepare to exit from the windows on Floor 3 , Side C, flames are visible on the exterior at the gable, but it appears that combustion is limited to the vinyl siding and soffit covering. There are no indicators of a significant fire in Exposure D at the time that the photo was taken. However, it is important to remember that this is a snapshot of conditions at one point in time from a single perspective.

Figure 2. Harrisonburg, VA Incident: Conditions on Side C

Note: Photo by Allen Litten

Potential Influencing Factors: The truss loft was likely divided between units by a 1 hour fire separation (generally constructed of gypsum board over the wood trusses). While providing a limited barrier to fire and smoke spread, it does not generally provide a complete barrier and smoke infiltration is likely. Sufficient smoke accumulation remote from the original fire location can present risk of a smoke explosion (see NIOSH Report 98-03 regarding a smoke explosion in Durango, Colorado restaurant). Alternately, fire extension into the truss loft above an exposure unit can result in ventilation controlled fire conditions, resulting in increased HRR if the void is opened (from above or below).

Extreme Fire Behavior: Smoke, air track, and flame indicators on Side C indicate that the fire in the truss loft may not have continued to develop past the initial ignition of accumulated smoke (fuel). It is possible that smoke accumulated in the truss loft above Exposure B and was ignited by subsequent extension from the fire unit. Depending on the fuel (smoke)/air mixture when flames extended into the space above Exposure B ignition could have resulted in a smoke explosion or a less violent fire gas ignition such as a flash fire.

Sandwich, MA

In the Sandwich incident, the extreme fire behavior occurred shortly after the hose team applied water to the soffit. However, this may or may not have been the precipitating event. As illustrated in Figure 3, the fire transitioned to a fully developed fire (likely due to the delay in suppression as the injured members were cared for). Blast effects on the structure are obvious.

Figure 3: Sandwich, MA: Conditions on Sides C and D

Note: Photos by Britt Crosby (http://www.capecodfd.com)

Potential Influencing Factors: The roof support system in this home appears to have been constructed of larger dimensional lumber (rather than lightweight truss construction). In addition, it is likely that the attic void spaces involved in this incident were large and complex (given the size of the dwelling and complex roof line). It appears that at least part of the home had a cathedral ceiling. Fire burning in the wood framing around the metal chimney would have allowed smoke (fuel) and hot gases to collect in the attic void in advance of fire extension.

Extreme Fire Behavior: The violence of the explosion (see blast damage to the roof on Side D in Figure 3) points to the potential for ignition of pre-mixed fuel (smoke) and air, resulting in a smoke explosion. However, it is also possible that failure of an interior ceiling (due to water or steam production from water applied through the soffit) could have increased ventilation to a ventilation controlled fire burning in the attic, resulting in a backdraft).

Fire Behavior Indicators

The information provided in news reports points to limited indication of potential for extreme fire behavior. One important question for each of us is how we can recognize this potential, even when indicators are subtle or even absent.

Important! A growth stage fire can present significant smoke and air track indicators, with increasing thickness (optical density), darkening color, and increasing velocity of smoke discharge. However, as discussed in The Hazard of Ventilation Controlled Fires, when the fire becomes ventilation controlled, indicators can diminish to the point where the fire appears to be in the incipient stage. This change in smoke and air track indicators was consistently observed during the full-scale fire tests of the influence of ventilation on fires in single-family homes conducted by UL earlier this year.

Even with an opening into another compartment or to the exterior of the building, a compartment fire can become ventilation controlled. Consider building factors including potential for fire and smoke extension into void spaces in assessing fire conditions and potential for extreme fire behavior. A ventilation controlled fire or flammable mixture of smoke and air may be present in a void space with limited indication from the exterior or even when working inside the structure.

Building Construction

Each of these incidents occurred in a wood frame structure. However, the construction in each case was somewhat different.

In Minneapolis, the house was likely balloon frame construction with full dimension lumber. As with many other structures with a “half-story”, the space under the pitched roof is framed out with knee walls to provide finished space. This design is not unique to legacy construction and may also be found with room-in-attic trusses. The void space behind the knee wall provides a significant avenue for fire spread. When involved in fire, opening this void space can quickly change fire conditions on the top floor as air reaches the (likely ventilation controlled) fire.

The incident in Harrisonburg involved a fire in a townhouse with the extreme fire behavior phenomena occurring in an exposure. While not reported, it is extremely likely that the roof support system was comprised of lightweight wood trusses. In addition, there was a reverse gable (possibly on Sides A and C) that provided an additional void. As previously indicated, the truss loft between dwelling units is typically separated by a one-hour rated draft stop. Unlike a fire wall, draft stops do not penetrate the roof and may be compromised by penetrations (after final, pre-occupancy inspection). Installed to code, draft stops slow fire spread, but may not fully stop the spread of smoke (fuel) into the truss lofts above exposures.

Firefighters in Sandwich were faced with a fire in an extremely large, wood frame dwelling. While the roof appeared to be supported by large dimensional lumber, it is likely that there were large void spaces as a result of the complex roofline. In addition, the framed out space around the metal chimney provided an avenue for fire and smoke spread from the lower level of the home to the attic void space.

Hazards and Tactics

Forewarned is forearmed! Awareness of the potential for rapid fire development when opening void spaces is critical. Given this threat, do not open the void unless you have a hoseline in hand (not just nearby).

Indirect attack can be an effective tactic for fires in void spaces. This can be accomplished by making a limited opening and applying water from a combination nozzle or using a piercing nozzle (which further limits introduction of air into the void).

If there are hot gases overhead, cool them before pulling the ceiling or opening walls when fire may be in void spaces. Pulses of water fog not only cool the hot gases, but also act as thermal ballast; reducing the potential for ignition should flames extend from the void when it is opened.

Lastly, react immediately and appropriately when faced with worsening fire conditions. Review my previous posts on Battle Drill (Part 1, Part 2, and Part 3). An immediate tactical withdrawal under the protection of a hoseline is generally safer than emergency window egress (particularly when ladders have not yet been placed to the window).

Ed Hartin, MS, EFO, MIFireE, CFO

Hazards Above

Thursday, July 8th, 2010

Finally! It has been quite some time since my last post, but the CFBT-US web site and blog have been attacked twice by hackers WordPress and ISP upgrade issues have been a major challenge and it has taken some time to get things back to normal.

A Big Improvement, But More Work is Needed

The Fire Service in the United States saw a considerable reduction in firefighter line-of-duty deaths in 2009. However, our efforts to improve firefighter safety must persist. Recent events reinforce the need to ensure understanding of practical fire dynamics and have the ability to apply this understanding on the fireground.

Three recent incidents involving extreme fire behavior present an opportunity to examine and reflect on the hazards presented by fires and accumulation of excess pyrolizate and unburned products of combustion in attics and other void spaces.

Minneapolis, MN Residential Fire

At 1130 hours on Saturday, July 3, 2010 Minneapolis firefighters responded to a residential fire at 1082 17th Avenue SE. First arriving companies observed light smoke and flames showing from a two and one-half story wood-frame home. A crew opening up the kneewall on the A/D corner of Floor 3 was trapped on the third floor by rapid fire progress.

Note: Photo by Steve Skar

A department spokesperson indicated that as they opened up the walls “it flashed over on them”. News reports indicated that the blast threw Firefighter Jacob LaFerriere, across the room and that he was able to locate a window, where he exited and dropped to the porch roof, one floor below. Capt. Dennis Mack was able to retreat into the stairwell where he was assisted to the exterior by other crews operating on the fireground (Mathews, 2010; Radomski & Theisen, 2010).

News reports also reported that a witness stated that the “flashover was quite loud and within seconds heavy fire was venting from the attic area” (Mathews, 2010). A later statements by department spokespersons indicated introduction of oxygen when the wall was opened resulted in the flashover (Porter, 2010) and that a burst of flames blew out the south side of the roof (Radomski & Theisen, 2010).

Firefighter Jacob LaFerriere suffered third degree burns on his arms and upper body. Capt. Dennis Mack suffered second degree burns (Radomski & Theisen, 2010) and are as of Sunday, July 4 were in satisfactory condition in the Hennepin County Medical Center Burn Unit.

Harrisonburg, VA Townhouse Fire

On June 24, 2010 Harrisonburg, Virginia firefighters responded to an apartment fire off Chestnut Ridge Drive. First arriving companies encountered a fire in a townhouse style, wood frame apartment. Investigating possible extension into Exposure Bravo, Firefighters Chad Smith and Bradly Clark observed smoke and then flames in the attic. They called for a hoseline, but when the pulled the ceiling, conditions worsened as the room ignited. Both firefighters escaped through a second floor window (head first, onto ladders placed by exterior crews). Four other firefighters were inside Exposure B when the extreme fire behavior occurred. Two received second degree burns, one was treated for heat exhaustion, and the fourth was uninjured (Firehouse.com News, 2010; WHSV, 2020). Department spokespersons indicated that a backdraft occurred when fire gases built up in the attic.


Note: Photo by Allen Litten

Sandwich MA Residential Fire

At around noon on Memorial Day, Sandwich, Massachusetts firefighters responded to a residential fire at 15 Open Trail Road. On arrival they found a 5,000 ft2 (464 m2) wood frame single-family dwelling with a fire on Side C (exterior) with extension into the home. Firefighters Daniel Keane and Lee Burrill stretched a handline through the door on Side A, knocking down the fire and extending the line out onto a deck on Side C. Fire was extending through a void containing a metal chimney flue on the exterior of the building. The crew on the hoseline was making good progress until they hit the soffit with a straight stream and an explosion occurred. The force of the blast knocked the crew over the deck railing and caused significant structural damage. Firefighter Keane suffered fractures of his neck and back while Firefighter Burrill experienced a severely fractured ankle (Fraser, 2010; D LeBlanc personal communication June 2010).

Note: Photos by Britt Crosby (http://www.capecodfd.com/)

Questions

One of these fires occurred in an older home of legacy construction, the other two occurred in relatively new buildings. One was a large contemporary home, likely with an open floor plan and large attic/trussloft voids. The other two occurred in buildings with smaller void spaces in the attic/trussloft.

  1. What is similar about these incidents and what is different?
  2. Based on the limited information currently available, what phenomena do you think occurred in each of the cases? What leads you to this conclusion?
  3. What indicators might have pointed to the potential for extreme fire behavior in each of these incidents?
  4. How might building construction have influenced fire dynamics and potential for extreme fire behavior in these incidents?
  5. What hazards are presented by fires in attics/trusslofts and what tactics may be safe and effective to mitigate those hazards?

Late Breaking Information

Two firefighters and an officer from the Wharton Fire Department were trapped by rapid fire progress in a commercial fire at the Maxim Production Company in Boling, TX on July 3, 2010. The crew had advanced a hoseline into the 35,000 ft2 (3252 m2) egg processing plant to cut off fire extension when they encountered rapidly worsening fire conditions. The two firefighters were able to escape, but Captain Thomas Araguz III was trapped and killed (Statter, D., 2010). More information will be provided on this incident as it becomes available.

References

Mathews, P. (2010). Two Minn. ffs burned in flashover. Retrieved July 4, 2010 from http://www.firehouse.com/news/top-headlines/two-minneapolis-firefighters-burned-flashover

Radomski, L & Theisen, S. (2010). Firefighters hospitalized after flashover identified. Retrieved July 4, 2010 from http://kstp.com/news/stories/S1637495.shtml?cat=1

Porter, K. (2010). 2 firefighters burned in Mpls. fire ID’d. Retrieved July 5, 2010 from http://www.kare11.com/news/news_article.aspx?storyid=856556&catid=396

WHSV. (2010) Harrisonburg firefighters talk about their close call. Retrieved July 5, 2010 from http://www.whsv.com/home/headlines/97127924.html

Firehouse.com News. (2010). Harrisonburg, Va. firefighters forced to bail out. Retrieved July 5, 2010 from http://www.firehouse.com/showcase/photostory/harrisburg-va-firefighters-have-bail-out

Fraser, D. (2010). Mass. firefighters thrown more than 30 Ft. by blast. Retrieved July 5, 2010 from http://www.firehouse.com/news/top-headlines/blast-throws-mass-firefighters-more-30-feet

Statter, D. (2010). Update: Captain Thomas Araguz III killed during 4-alarm fire at egg plant in Boling, Texas. http://statter911.com/2010/07/04/firefighter-killed-during-4-alarm-fire-at-egg-plant-details-from-wharton-county-texas/

Reading the Fire 14

Monday, April 19th, 2010

It has been a number of months since the last Reading the Fire post. It is essential to continue the process of deliberate practice in order to continue to improve and refine skill in Reading the Fire.

As we start the New Year it is a good time to reaffirm our commitment to mastering our craft. Developing and maintaining proficiency in reading the Fire using the B-SAHF (Building, Smoke, Air Track, Heat, and Flame) organizing scheme for fire behavior indicators, requires practice. This post provides an opportunity to exercise your skills using a video segment shot during a residential fire.

Residential Fire

In mid-January 2010, the Gary, Indiana Fire Department was dispatched to a residential fire on Massachusetts Street at East 24th Avenue, on arrival Battalion 4 advised of a working fire in a 2 story dwelling. While the first arriving engine was laying a supply line from a nearby hydrant, the first in truck forced entry.

Download and the B-SAHF Worksheet.

Watch the first 35 seconds (0:35) of the video. This segment was shot from Side A. First, describe what you observe in terms of the Building, Smoke, Air Track, Heat, and Flame Indicators; then answer the following five standard questions?

  1. What additional information would you like to have? How could you obtain it?
  2. What stage(s) of development is the fire likely to be in (incipient, growth, fully developed, or decay)?
  3. What burning regime is the fire in (fuel controlled or ventilation controlled)?
  4. What conditions would you expect to find inside this building? If presented with persons reported (as the first arriving companies were) how would you assess potential for victim survival?
  5. How would you expect the fire to develop over the next two to three minutes

Now watch the remainder of the video clip and answer the following questions:

  1. Did fire conditions progress as you anticipated?
  2. A voice heard in the video states that this was a backdraft. Do you agree? Why or why not?

It is likely that the first in truck company in this incident made entry to search for occupants and to locate the fire. Regardless of your perspective on search with or without a hoseline, this video clip provides lessons.

  • It is essential to read the fire, recognize the stage(s) of fire development and burning regime(s) in the involved compartments.
  • In addition to reading current conditions, anticipate likely fire development and potential for extreme fire behavior.
  • Making entry (and leaving the door fully open) creates a ventilation opening (inlet, exhaust, or both). Recognize the potential influence of changes to the ventilation profile on fire behavior.
  • To borrow a phrase from a number of National Institute for Occupational Safety and Health Death in the Line of Duty reports; Ventilation and fire attack must be closely coordinated. One key element in this coordination is that charged lines must be in place before completion of ventilation openings. This is critical when dealing with a ventilation controlled fire.

Master Your Craft

Ed Hartin, MS, EFO, MIFIreE, CFO

Chicago Extreme Fire Behavior
Analysis of Fire Behavior Indicators

Monday, March 15th, 2010

Quick Review

The previous post in this series presented a video clip of an incident on the afternoon of February 18, 2010 that injured four Chicago firefighters during operations at a residential fire at 4855 S. Paulina Street.

First arriving companies discovered a fire in the basement of a 1-1/2 story, wood frame, single family dwelling and initiated fire attack and horizontal ventilation of the floors above the fire. Based on news accounts, the company assigned to fire attack was in the stairwell and another firefighter was performing horizontal ventilation of the floors above the fire on Side C when a backdraft or smoke explosion occurred. Two firefighters on the interior, on at the doorway and the firefighter on the ladder on Side C were injured and were transported to local hospitals for burns and possible airway injuries.

In analyzing the video clip shot from inside a nearby building, we have several advantages over the firefighters involved in this incident.

Time: We are not under pressure to make a decision or take action.

Reduced Cognitive Workload: Unlike the firefighters who needed to not only read the fire, but also to attend to their assigned tactics and tasks, our only focus is analysis of the fire behavior indicators to determine what (if any) clues to the potential for extreme fire behavior may have been present.

Repetition: Real life does not have time outs or instant replay. However, our analysis of the video can take advantage of our ability to pause, and replay key segments, or the entire clip as necessary.

Perspective: Since the field of view in the video clip is limited by the window and the fidelity of the recording is less than that seen in real life, it presents a considerably different field of view than that of the firefighters observed in operation and does not allow observation of fire behavior indicators and tactical operations on Sides A, B, and D.

Initial Size-Up

What B-SAHF indicators could be observed on Side C up to the point where firefighters began to force entry and ventilate the basement (approximately 02:05)?

Figure 1. Conditions at 01:57 Minutes Elapsed Time in the Video Clip

0157_time

Building: The structure is a 1-1/2 story, wood frame, dwelling with a daylight basement. The apparent age of the structure makes balloon frame construction likely, and the half story on the second floor is likely to have knee walls, resulting in significant void spaces on either side and a smaller void space above the ceiling on Floor 2. One window to the left of the door on Side C appears to be covered with plywood (or similar material). Given the location of the door (and door on Side A illustrated in the previous post in this series), it is likely that the stairway to the basement is just inside the door in Side C and a stairway to Floor 2 is just inside the door on Side A.

Smoke: A moderate volume of dark gray smoke is visible from the Basement windows and windows and door on Floor 1 as well as a larger volume from above the roofline on Side B. While dark, smoke on Side C does not appear to be thick (optically dense), possibly due to limited volume and concentration while smoke above the roofline on Side B appears to be thicker. However smoke on Side C thickens as time progresses, particularly in the area of the door on Floor 1. The buoyancy of smoke is somewhat variable with low buoyancy on Side C and greater buoyancy on Side B. However, smoke from the area of the door on Floor 1 Side C intermittently has increased buoyancy.

Air Track: Smoke on Side C appears to have a faintly pulsing air track with low velocity which is masked to some extent by the effects of the wind (swirling smoke due to changes in low level wind conditions). Smoke rising above the roofline on Side B appears to be moving with slightly greater velocity (likely due to buoyancy).

Heat: The only significant heat indicators are limited velocity of smoke discharge and variations in buoyancy of smoke visible from Sides B and C. Low velocity smoke discharge and low buoyancy of the smoke on Side C points to relatively low temperatures inside the building. The greater buoyancy and velocity of smoke observed above the roofline on Side B indicates a higher temperature in the area from where this smoke is discharging (likely a basement window on Side B).

Flame: No flames are visible.

Initial Fire Behavior Prediction

Based on assessment of conditions to this point, what stage(s) of development and burning regime(s) is the fire likely to be in?

Dark smoke with a pulsing air track points to a ventilation controlled, decay stage fire.

What conditions would you expect to find inside the building?

Floors 1 and 2 are likely to be fully smoke logged (ceiling to floor) with fairly low temperature. The basement is likely to have a higher temperature, but is also likely to be fully smoke logged with limited flaming combustion.

How would you expect the fire to develop over the next few minutes?

As ventilation is increased (tactical ventilation and entry for fire control), the fire in the basement will likely remain ventilation controlled, but will return to the growth stage as the heat release rate increases. Smoke thickness and level (to floor level) along with a pulsing air track points to potential for some type of ventilation induced extreme fire behavior such as ventilation induced flashover (most likely) or backdraft (less likely). Another possibility, would be a smoke explosion; ignition of premixed gas phase fuel (smoke) and air that is within its flammable range (less likely than some type of ventilation induced extreme fire behavior)

Ongoing Assessment

What indicators could be observed while the firefighter was forcing entry and ventilating the daylight basement on Side C (02:05-02:49)?

There are few changes to the fire behavior indicators during this segment of the video. Building, Heat, and Flame indicators are essentially unchanged. Smoke above the roofline appears to lighten (at least briefly) and smoke on Side C continues to show limited buoyancy with a slightly pulsing air track at the first floor doorway.

What B-SAHF indicators can be observed at the door on Side C prior to forced entry (02:49-03:13)?

Figure 2. Conditions at 03:06 Minutes Elapsed Time in the Video Clip

0307_time

Figure 3. Conditions at 03:08 Minutes Elapsed Time in the Video Clip

0308_time

Building, Smoke, Heat and Flame indicators remain the same, but several more pulsations (03:05-03:13) providing a continuing, and more significant indication of ventilation controlled, decay stage fire conditions.

What indicators can be observed at the door while the firefighter attempts to remove the covering over the window adjacent to the door on Floor 1 (03:13-13:44)?

No significant change in Building, Heat, or Flame Indicators. However, smoke from the doorway has darkened considerably and there is a pronounced pulsation as the firefighter on the ladder climbs to Floor 2 (03:26). It is important to note that some of the smoke movement observed in the video clip is fire induced, but that exterior movement is also significantly influenced by wind.

What B-SHAF indicators do you observe at the window on Floor 2 prior to breaking the glass (03:44)?

Figure 4. Conditions at 03:43 Minutes Elapsed Time in the Video Clip

0343_time

The window on Floor 2 is intact and appears to be tight as there is no smoke visible on the exterior. It is difficult to tell due to the angle from which the video was shot (and reflection from daylight), but it would be likely that the firefighter on the ladder could observe condensed pyrolizate on the window and smoke logging on Floor 2. It is interesting to note limited smoke discharge from the top of the door and window on Floor 1 in the brief period immediately prior to breaking the window on Floor 2.

What indicators are observed at the window on Floor 2 immediately after breaking the glass (03:44-03:55)?

Figure 5. Conditions at 03:52 Minutes Elapsed Time in the Video Clip

0352_time

No significant changes in Building, Heat, or Flame indicators. Dark gray smoke with no buoyancy issues from the window on Floor 2 with low to moderate velocity immediately after the window is broken.

What B-SAHF indicators were present after the ventilation of the window on Floor 2 Side C was completed and 04:08 in the video clip (03:44-04:08)?

Buoyancy and velocity both increase and a slight pulsing air track develops within approximately 10 seconds. In addition, the air track at the door on Floor 1 shifts from predominantly outward with slight pulsations to predominantly inward, but with continued pulsation (possibly due to the limited size of the window opening on Floor 2, Side C.

Anticipating Potential Fire Behavior

Unlike the firefighters in Chicago who were operating at this incident, we can hit the pause button and consider the indicators observed to this point. Think about what fire behavior indicators are present (and also consider those that are not!).

Initial observations indicated a ventilation controlled decay stage fire and predicted fire behavior is an increase in heat release rate with potential for some type of extreme fire behavior. Possibilities include ventilation induced flashover (most likely) or backdraft (less likely), or smoke explosion (less likely than some type of ventilation induced extreme fire behavior).

Take a minute to review the indicators of ventilation controlled, decay stage fires as illustrated in Table 1.

Table 1. Key Fire Behavior Indicators-Ventilation Controlled, Decay Stage Fires

vent_controlled_decay

Which of these indicators were present on Side C of 4855 S. Paulina Street?

Building: The building appeared to be unremarkable, a typical single family dwelling. However, most residential structures have more than enough of a fuel load to develop the conditions necessary for a variety of extreme fire behavior phenomena.

Smoke: The dark smoke with increasing thickness (optical density) is a reasonably good indicator of ventilation controlled conditions (particularly when combined with air track indicators). Lack of buoyancy indicated fairly low temperature smoke, which could be an indicator of incipient or decay stage conditions or simply distance from the origin of the fire. However, combined with smoke color, thickness, and air track indicators, this lack of buoyancy at all levels on Side C is likely an indicator of dropping temperature under decay stage conditions. This conclusion is reinforced by the increase in buoyancy after ventilation of the window on Floor 2 (increased ventilation precipitated increased heat release rate and increasing temperature).

Air Track: Pulsing air track, while at times quite subtle and masked by swirling smoke as a result of wind, is one of the strongest indications of ventilation controlled decay stage conditions. While often associated with backdraft, this indicator may also be present prior to development of a sufficient concentration of gas phase fuel (smoke) to result in a backdraft.

Heat: Velocity of smoke discharge (air track) and buoyancy (smoke) are the only two heat indicators visible in this video clip. As discussed in conjunction with smoke indicators, low velocity and initial lack of buoyancy which increases after ventilation is indicative of ventilation controlled, decay stage conditions.

Flame: Lack of visible flame is often associated with ventilation controlled decay and backdraft conditions. However, there are a number of incidents in which flames were visible prior to occurrence of a backdraft (in another compartment within the structure). Lack of flames must be considered in conjunction with the rest of the fire behavior indicators. In this incident, lack of visible flames may be related to the stage of fire development, but more likely is a result of the location of the fire, as there is no indication that flames were present on Side C prior to the start of the video clip.

What Happened?

Firefighters had entered the building for fire attack while as illustrated in the video clip, others were ventilating windows on Side C. It is difficult to determine from the video if a window or door at the basement level on Side C was opened, but efforts were made to do so. A window on Floor 2 had been opened and firefighters were in the process of removing the covering (plywood) from a window immediately adjacent to the door on Floor 1. At 04:12, an explosion occurred, injuring two firefighters on the interior as well as the two firefighters engaged in ventilation operations on Side C.

Starting at approximately 03:59, velocity of smoke discharge from the window on Floor 2 Side C increases dramatically. At 04:08 discharge of smoke begins to form a spherical pattern as discharged from the window. This pattern becomes more pronounced as the sphere of smoke is pushed away from the window by increasing velocity of smoke discharge at 04:12, immediately prior to the explosion. Velocity of smoke discharge at the door increases between 03:59 and -4:12 as well, but as the opening is larger, this change is less noticeable. As pressure increases rapidly during the explosion a whooshing sound can be heard. After the explosion, there was no noticeable increase in fire growth.

Figure 6. Conditions at 04:08 Minutes Elapsed Time in the Video Clip

0408_time

Figure 7. Conditions at 04:09 Minutes Elapsed Time in the Video Clip

0409_time

Figure 8. Conditions at 04:10 Minutes Elapsed Time in the Video Clip

0410_time

Figure 9. Conditions at 04:11 Minutes Elapsed Time in the Video Clip

0411_time

Figure 10. Conditions at 04:12 Minutes Elapsed Time in the Video Clip

0412_time

Figure 11. Conditions at 04:13 Minutes Elapsed Time in the Video Clip

0413_time

Based on observation of fire behavior indicators visible in the video clip, we know that a transient extreme fire behavior event occurred while a crew was advancing a hoseline on the interior and ventilation operations were being conducted on Side C. What we dont know is what firefighting operations were occurring on the other sides of the building or in the interior. In addition, we do not have substantive information from the fire investigation that occurred after the fire was extinguished.

The Ontology of Extreme Fire Behavior presented in an earlier post classifies these types of phenomena on the basis of outcome and conditions. As a transient and explosive event, this was likely a backdraft or smoke explosion. In that this occurred following entry and during ongoing ventilation operations, I am inclined to suspect that it was a backdraft.

Indicators visible on Side C provided a subtle warning of potential for some type of ventilation induced extreme fire behavior, but were likely not substantially different from conditions observed at many fires where extreme fire behavior did not occur.

As the title of the wildland firefighting course S133 states; Look Up, Look Down, Look Around! Anticipation of fire development and extreme fire behavior requires not only recognition of key indicators, but that these indicators be viewed from a holistic perspective. Firefighters and/or officers performing a single task or tactical assignment may only see part of the picture. It is essential that key indicators be communicated to allow a more complete picture of what is occurring and what may occur as incident operations progress.

Ed Hartin, MS, EFO, MIFireE, CFO

Did You Ever Wonder?

Thursday, December 24th, 2009

The ability to read the fire and predict likely fire behavior is a critical skill for both firefighters and fire officers. Previous posts have examined how to use the B-SAHF scheme to recognize critical fire behavior indicators and identify the stage of fire development, burning regime, and potential for extreme fire behavior such as flashover or backdraft. However, there is something missing!

Experience is critical to adapting standard procedures and practices to a complex and dynamic operational environment. However, learning about fire behavior and changes in fire conditions based on fireground observations are a bit like a black box test. Black box testing is a technique for testing computer software in which the internal workings of the item being tested are not known by the tester. This is not entirely true in the case of fire behavior, but there is much that we dont know when assessing conditions on the fireground. How long has the fire been burning? What are the specific characteristics of the fuel? What sort of internal compartmentation is present? What exactly is the ventilation profile? Some of these factors can be determined during fire investigation and it is also possible to determine (with some degree of uncertainty) what influence these factors had on the outcome of the incident. Did you ever wonder how fire behavior would have changed if you had used different tactics? Unfortunately, in real life there are no do overs!

UL Tactical Ventilation Research Project

One of the people who has asked himself the question of what would have changed if different tactics were used is Underwriters Laboratories Fire Protection Engineer Steve Kerber.

Underwriters Laboratories (UL) has received a Firefighter Safety Research and Development Grant from the Department of Homeland Security (DHS). This research project will investigate and analyze the impact of natural horizontal ventilation on fire development and conditions in legacy (older, more highly compartmented) and contemporary (multi-level, open floor plan) residential structures.

Preliminary work has included review of literature related to horizontal ventilation and incidents in which ventilation had a significant influence on firefighter injuries and fatalities. In addition, UL has done preliminary work on the performance of various structural components such as single and multi-pane windows as preliminary input for design of full scale residential fire experiments.

In mid-December 2009, Steve Kerber met with the project advisory panel comprised of Captain Charles Bailey, Montgomery County (MD) Fire Department; Lieutenant John Ceriello New York City Fire Department, Firefighter James Dalton and Director of Training Richard Edgeworth, Chicago Fire Department, Chief Ed Hartin, Central Whidbey Island (WA) Fire & Rescue, Chief Otto Huber Loveland-Symmes (OH) Fire Department, and Chief Mark Nolan, Northbrook (IL) Fire Department. In addition, the advisory panel includes Fire Protection Engineers Dan Madrzykowski from the National Institute of Standards and Technology (NIST) and Dr. Stefan Svensson, a research and development engineer from the Swedish Civil Contingencies Agency.

Figure 1. Defining Experiment Parameters for the Contemporary Structure

kerber_plans

The main task presented to the advisory panel at the first meeting was to aid in defining the parameters for the experiment; including fire location, changes in ventilation profile, timing of these changes, and instrumentation to measure effects on fire development and conditions.

UL Large Fire Research Facility

The ventilation experiments will be conducted at the UL Large Fire Research Facility in Northbrook, IL. From the exterior, this facility simply looks like a large industrial building (see Figure 2). However, the interior of the structure includes a unique facility for fire research.

Figure 2. UL Large Fire Research Facility

ul_large_fire_lab_outside

One of the facilities inside this building is a 100 x 120 (30.48 m x 36.58 m) with a ceiling height that is adjustable up to 50 (15.24 m) (see Figure 3). All of the smoke resulting from tests in this facility is exhausted through a system designed to oxidize unburned fuel and scrub hazardous products from the effluent prior to discharge to the atmosphere. Tests are monitored from a control room that overlooks the large burn room.

Figure 3. Large Burn Room

ul_large_fire_lab_inside

Over the next month, the two residential structures to be used for the ventilation experiments will be constructed inside the large burn room at the UL Large Fire Test Facility. After construction is complete, a series of 16 full scale fire experiments is planned to evaluate a range of different horizontal ventilation scenarios.

Research with the Fire Service

Steve Kerber has often stated that it is essential that scientists and engineers conduct research with, not for, the fire service. Engagement between researchers and firefighters on the street is essential in advancement of our profession. With this ventilation research project, Underwriters Laboratories is actively engaged in this process.

The outcome of this project will not simply be an academic paper (but there might be one or more of those as well). As part of the DHS grant, UL will be developing an on-line course to present the results of the experiments and their practical application on the fireground.

Happy Holidays,

Ed Hartin, MS, EFO, MIFireE, CFO

Decay Stage Fires:
Key Fire Behavior Indicators

Thursday, October 29th, 2009

As discussed in Flashover and Fully Developed Fires: Key Fire Behavior Indicators, providing additional oxygen to a ventilation controlled fire will result in a corresponding increase in heat release rate (HRR). This occurs because oxygen is required to release the chemical potential energy in fuel. The energy released per unit of mass of oxygen is remarkably consistent for both natural and synthetic organic (carbon containing) fuels.

Thorntons Rule specifies that one kilogram (1 kg) of oxygen is required to release 13.1 mega joules (MJ) of energy. Multiplying 13.1 MJ/kg of oxygen by 21% (the concentration of oxygen in air) provides a value of 2.751 MJ/kg of air. The Society of Fire Protection Engineering (SFPE) Handbook of Fire Protection Engineering (SFPE, 2002) rounds this value to 3.0 MJ/kg of air. For a more detailed discussion of Thorntons Rule and the relationship between fuel, oxygen, and energy release, see Fuel and Ventilation.

Decay Stage

A compartment fire may enter the decay stage as the available fuel is consumed or due to limited oxygen. As discussed in relation to flashover, a fuel package that does not contain sufficient energy or does not have a sufficient heat release rate to bring a compartment to flashover, will pass through each of the stages of fire development (but may not extend to other fuel packages). On a larger scale, without intervention an entire structure may reach full involvement and as fuel is consumed move into the decay stage. However, there is another, more problematic way for the fire to move into the decay stage. When the ventilation profile of the compartment or building does not provide sufficient oxygen, the fire may move into the decay stage. Heat release rate decreases as oxygen concentration drops. While temperature follows heat release rate, the temperature in decay stage fire may remain high for some time (particularly in well insulated, energy efficient buildings). This presents a significant threat as solid fuel packages continue to pyrolize and the involved compartment(s) may contain a high concentration of hot, pyrolized fuel, and flammable gaseous products of incomplete combustion.

Ventilation Controlled Fires

Under ventilation controlled conditions excess pyrolizate and flammable products of combustion present in smoke are a significant hazard to firefighters. Lets go back to the fire triangle to examine the nature of this threat. While fuel, heat, and oxygen are present in proportion to support combustion where the fire is burning, the heat of the fire is pyrolyzing more fuel vapor than the fire can consume. In addition, incomplete combustion results in production of flammable gases such as carbon monoxide. The speed of fire development is limited by the availability of atmospheric oxygen provided by the current ventilation profile of the compartment or building.

In his presentation, Fire Dynamics for the Fire Service, Dan Madrzykowski of the National Institute of Standards and Technology (NIST) discussed the increased potential for ventilation controlled, decay stage fires in todays modern, energy efficient structures. Dan presented the time temperature curve illustrated in Figure 1 to describe modern fire development and the potential influence of firefighting tactics.

Figure 1. Fire Development in the Modern Environment

modern_fire_development

Note: Adapted from National Institute of Standards and Technology (NIST) Fire Dynamics for the Fire Service, D. Madryzkowski.

The data in Figure 1 could be presented as HRR over time as well, but as HRR cannot be measured outside the lab, temperature is often used to describe fire development in full-scale tests. When the fire is burning in a ventilation controlled state, any increase in the supply of oxygen to the fire will result in an increase in heat release rate. Increase in ventilation may result from firefighters making entry into the building (the access point is a ventilation opening), tactical ventilation (performed by firefighters), or unplanned ventilation (e.g., failure of window glazing due to elevated temperature).

It is essential to recognize when the fire is, or may be ventilation controlled and the influence of planned and unplanned changes in ventilation profile. Most compartment fires that progress into the growth stage are ventilation controlled when the fire department arrives. A bi-directional air track (smoke out the top and air in the bottom) is often a significant indicator of a ventilation controlled fire, but what about before the door is open?

Figure 2. Assessment of Conditions at the Door

door_questions

As combustion becomes more incomplete, smoke production increases, color darkens, and optical density increases. However, these indicators may be subtle when observing fire conditions from the exterior. Assessment of conditions must continue after making entry. Smoke and air track indicators can be particularly useful in addressing the stage of fire development and burning regime when working inside. In addition, flames moving through the hot gas layer are a strong indicator of a ventilation controlled fire (as well as a threat to your safety which should be dealt with immediately).

Ventilation Induced Extreme Fire Behavior

When the fire is ventilation controlled, increased air supply to the fire will result in increased heat release rate and depending on conditions may result in extreme fire behavior such as flashover or backdraft. While both phenomena result from an increase in ventilation, vent induced flashover and backdraft are different phenomena. The conditions required for a ventilation induced flashover are 1) a compartment fire which has an insufficient HRR to reach flashover due to ventilation controlled combustion, and 2) insufficient concentration of excess pyrolizate and unburned products of incomplete combustion to result in a backdraft. While complex, the key determinant in the occurrence of a backdraft is likely to be the concentration of gas phase fuel within the compartment.

While these phenomena are different, both present a significant threat to firefighters. Rapid fire progress due to ventilation induced flashover or backdraft is not an instantaneous process. Depending on a number of variables such as the location of the fire, current level of involvement, temperature of the smoke (hot gas) layer, and extent of the increase in ventilation these rapid fire progress phenomenon may take some time to occur. However, when it does, fire development will be extremely rapid! Firefighters entering a compartment or building containing an under ventilated fire must be aware of and manage the hazards presented by the potential for rapid fire progress. Remember, many if not most fires that have progressed beyond the incipient stage before firefighters arrival are ventilation controlled and present the potential for rapid fire progress with increased ventilation (see Situational Awareness is Critical).

Figure 3 lists the fire behavior indicators related to ventilation controlled decay stage conditions and the potential for ventilation induced extreme fire behavior. It is important to note that there are not always clear distinctions in the visual indicators for vent induced flashover and backdraft.

Figure 3. FBI: Decay Stage

decay_indicators

Be Wary

Decay stage indicators can sometimes be subtle and conditions may not look too bad (maybe like an incipient or early growth stage fire if you are not paying close attention and consider the possibilities).

It is often assumed (incorrectly) that ventilation induced extreme fire behavior (flashover or backdraft) will occur immediately after an increase in ventilation. Depending on fire conditions and building configuration there may be a significant time lag between ventilation and resulting changes in fire behavior. When ventilation controlled decay conditions are indicated (or suspected), firefighters should move cautiously and take action to change conditions inside the building or compartment (e.g., gas cooling, ventilation).

You have responded to a fire in a one-story single family dwelling of wood frame construction. A fire which started in a bedroom on the Alpha Bravo corner of the structure has gone from fully developed to the decay stage due to a lack of oxygen as building openings (doors and windows) remain closed and intact.

  • What conditions would you expect to see from the exterior of the structure?
  • What indicators may be visible from the front door as you make entry?

A fire in the decay stage (particularly when this is due to limited oxygen) still presents a significant threat as conditions can change rapidly.

  • If the door at your entry point remains fully open, how will this influence fire behavior (assuming no other ventilation has been performed)?
  • How would fire behavior be influenced if a window (or windows) in the fire compartment are opened along with the door at your entry point?
  • What indicators would you anticipate observing as you traveled through the living room to the hallway leading to the bedroom?
  • What conditions would you find in the hallway outside the fire compartment?

After making entry, consider if conditions are different than you anticipated?

  • Why might this be the case?
  • What differences in conditions would be cause for concern?

Late Breaking News

I have been selected to serve as Fire Chief with the Central Whidbey Island Fire District in Washington and anticipate starting in my new position by mid November.

Over the next year I will also be serving on an advisory panel to assist Underwriters Laboratory with a research project on to examine the impact of ventilation on fire behavior in legacy and contemporary construction. Output from this project will include a formal technical report, articles in fire service publications, presentation to the fire service community, and a stand-alone web-based training module.

References

Society of Fire Protection Engineers (SFPE). (2002). The SFPE handbook of fire protection engineering (3rd ed.). Quincy, MA: National Fire Protection Association.

Madrzykowski, D. Fire dynamics for the fire service [PowerPoint Presentation], Gaithersburg, MD: National Institute of Standards and Technology.

Fully Developed Fires:
Key Fire Behavior Indicators

Thursday, October 22nd, 2009

This post continues examination of key indicators used to recognize stages of fire development (i.e., incipient, growth, fully developed, and decay), burning regimes (i.e., fuel and ventilation controlled) with a look at indicators of the fully developed stage of fire development. Most buildings are comprised of multiple, interconnected compartments and fire conditions can vary widely from compartment to compartment. Fire in the compartment of origin may have reached the fully developed stage, while adjacent compartments may have just entered the growth stage.

Figure 1. Fully Developed Fire

fully_developed_fire

National Institute for Occupational Safety and Health (NIOSH) Death in the Line of Duty Report F2007-02 (2009) recommends that fire service agencies: Train fire fighters to recognize the conditions that forewarn of a flashover/flameover [rollover] and communicate fire conditions to the incident commander as soon as possible (p. 2). Note: flameover and Rollover are synonyms.

Flameover (Rollover): The condition where unburned fuel (pyrolyzate) from the originating fire has accumulated in the ceiling layer to a sufficient concentration (i.e., at or above the lower flammable limit) that it ignites and burns; can occur without ignition of, or prior to, the ignition of other fuels separate from the origin. (NFPA 921, 2008, 3.3.67 and 3.3.137)

Recognition of key fire behavior indicators is critical. However, communication of this information to the incident commander (as it may impact on strategies) alone is not sufficient. Companies working in the fire environment must proactively mitigate this threat through effective fire control and ventilation strategies and tactics.

Flashover

Flashover is the sudden transition from a growth stage to fully developed fire. When flashover occurs, there is a rapid transition to a state of total surface involvement of all combustible material within the compartment. Conditions for flashover are defined in a variety of different ways. In general, ceiling temperature in the compartment must reach 500o-600o C (932o-1112o F) or the heat flux (a measure of heat transfer) to the floor of the compartment must reach 15-20 kW/m2 (1.32 Btu/s/ft2)-1.76 Btu/s/ft2). When flashover occurs, burning gases will push out openings in the compartment (such as a door leading to another room) at a substantial velocity (Karlsson & Quintiere, 2000).

It is important to remember that flashover does not always occur. There must be sufficient fuel and oxygen for the fire to reach flashover. If the initial object that is ignited does not contain sufficient energy (heat of combustion) and does not release it quickly enough (heat release rate), flashover will not occur (e.g., small trash can burning in the middle of a large room). Likewise, if the fire sufficiently depletes the available oxygen, heat release rate will drop and the fire in the compartment will not reach flashover (e.g., small room with sealed windows and the door closed). A fire that fails to reach a sufficient heat release rate for flashover to occur due to limited ventilation presents a significant hazard as increased ventilation may result in a ventilation induced flashover (see Understanding Flashover: Myths & Misconceptions Part 2 and The Ventilation Paradox).

Indicators of Flashover Potential

Recognizing flashover and understanding the mechanisms that cause this extreme fire behavior phenomenon is important. However, the ability to recognize key indicators and predict the probability of flashover is even more important. Indicators of potential or impending flashover are listed in Figure 2.

Figure 2. Indicators of Potential Flashover

flashover_indicators

If the fire in our residential scenario is nearing flashover (in the compartment of origin) what fire behavior indicators might be observed? Use the B-SAHF model to help you frame your answers.

You have responded to a fire in a one-story single family dwelling of wood frame construction. A fire which started in a bedroom on the Alpha Bravo corner of the structure is nearing flashover. A thick hot gas layer has developed in the bedroom and is flowing out the open door into the hallway. The fire has extended to the bed and flames in the plume have reached the ceiling and have begun to extend horizontally in the ceiling jet. Fuel packages below the level of the hot gas layer (e.g., furniture, carpet, and contents) are beginning to pyrolize.

  • What conditions would you expect to see from the exterior of the structure?
  • What indicators may be visible from the front door as you make entry?

Remember that fire conditions will vary throughout the building. While the fire is in the growth stage and nearing flashover in the bedroom, conditions may be different in other compartments within the building.

  • What indicators would you anticipate observing as you traveled through the living room to the hallway leading to the bedroom?
  • What conditions would you find in the hallway outside the fire compartment?
  • After making entry, consider if conditions are different than you anticipated?
  • Why might this be the case?
  • What differences in conditions would be cause for concern?
  • How might your answers to the preceding questions have differed if the bedroom door was closed and fire growth limited by ventilation?

Fully Developed Fire

At this post-flashover stage, energy release is at its greatest, but is generally limited by ventilation (more on this in a bit). Unburned gases accumulate at the ceiling level and frequently burn as they leave the compartment, resulting in flames showing from doors or windows. The average gas temperature within a compartment during a fully developed fire ranges from 700o-1200o C (1292o-2192o F)

Remember that the compartment where the fire started may reach the fully developed stage while other compartments have not yet become involved. Hot gases and flames extending from the involved compartment transfer heat to other fuel packages (e.g., contents, compartment linings, and structural materials) resulting in fire spread. Conditions can vary widely with a fully developed fire in one compartment, a growth stage fire in another, and an incipient fire in yet another. It is important to note that while a fire in an adjacent compartment may be incipient, conditions within the structure are immediately dangerous to life and health (IDLH).

Indicators of a Fully Developed Fire

Remember that a fully developed fire refers to conditions within a given compartment or compartments. It does not necessarily mean that the entire building is fully involved. Figure 3 lists indicators of fully developed fire conditions.

Figure 3. FBI-Fully Developed Stage

fully_developed_indicators

If the fire in our residential scenario has progressed to the fully developed stage (in the compartment of origin) what fire behavior indicators might be observed? Use the B-SAHF model to help you frame your answers.

You have responded to a fire in a one-story single family dwelling of wood frame construction. A fire which started in a bedroom on the Alpha Bravo corner of the structure has reached the fully developed stage and now involves the contents of the room and interior finish of this compartment.

  • What conditions would you expect to see from the exterior of the structure?
  • What indicators may be visible from the front door as you make entry?

Remember that fire conditions will vary throughout the building. While the fire is fully developed in the bedroom, conditions may be different in other compartments within the building.

  • What indicators would you anticipate observing as you traveled through the living room to the hallway leading to the bedroom?
  • What conditions would you find in the hallway outside the fire compartment?
  • After making entry, consider if conditions are different than you anticipated?
  • Why might this be the case?
  • What differences in conditions would be cause for concern?

Ventilation Controlled Fires

When the fire is burning in a ventilation controlled state, any increase in the supply of oxygen to the fire will result in an increase in heat release rate. Increase in ventilation may result from firefighters making entry into the building (the access point is a ventilation opening), tactical ventilation (performed by firefighters), or unplanned ventilation (e.g., failure of window glazing due to elevated temperature).

It is essential to recognize when the fire is, or may be ventilation controlled, and the influence of planned and unplanned changes in ventilation profile on fire behavior. Most compartment fires in the late growth stage or which are fully developed are ventilation controlled when the fire department arrives. Even if the fire has not entered the decay stage due to limited ventilation, the increased oxygen provided by increases in ventilation (such as that caused by opening the door to make entry) will increase heat release rate. This is not to say that increased ventilation is a bad thing, but firefighters should be prepared to deal with this change in fire behavior.

Master Your Craft

Remember the Past

Line of duty deaths involving extreme fire behavior has a significant impact on the family of the firefighter or firefighters involved as well as their department. Department investigative reports and NIOSH Death in the Line of Duty reports point out lessons learned from these tragic events. However, as time passes, these events fade from the memory of those not intimately connected with the individuals involved. It is important that we remember the lessons of the past as we continue our study of fire behavior and work to improve firefighter safety and effectiveness on the fireground.

October 29, 2008
Firefighter Adam Cody Renfroe
Crossville Fire Department, Alabama

The Crossville Fire Department was dispatched to a fire in a single-family residence. was on the first engine to arrive on the scene to find thick, black smoke from the roof and a report that all occupants were out of the house.

Firefighter Renfroe and another firefighter advanced a hoseline to the front door of the residence. He sent the other firefighter back to the fire truck for a tool. When the firefighter returned, Firefighter Renfroe was gone and the nozzle remained by the doorway. At about the same time, the fire inside of the structure intensified. Firefighter Renfroe transmitted a distress message from the interior. Firefighters were not immediately able to enter the structure due to fire conditions.

Firefighters discovered Firefighter Renfroe about 4 feet from the homes back door, but By the time firefighters reached him, he was deceased. The cause of death was smoke inhalation and thermal burns.

For more information on this incident, see NIOSH Death in the Line of Duty Report F2008-34.

Ed Hartin, MS, EFO, MIFireE, CFO

References

Karlson, B. & Quintiere, J. (2000) Enclosure fire dynamics. Boca Raton, FL: CRC Press.

National Institute for Occupational Safety and Health (NIOSH). (2009). Death in the Line of Duty Report F2007-02. Retrieved October 22, 2009 from http://www.cdc.gov/niosh/fire/pdfs/face200702.pdf .