Posts Tagged ‘practical fire dynamics’

Influence of Ventilation in Residential Structures:
Tactical Implications Part 8

Friday, January 13th, 2012

The eighth and tenth tactical implications identified in the Underwriters Laboratories study of the Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction (Kerber, 2011) are the answer to the question, can you vent enough and the influence of pre-existing openings or openings caused by fire effects on the speed of progression to flashover.

The ninth implication; the effects of closed doors on tenability for victims and firefighters, will be addressed in the next post.

Photo Credit: Captain Jacob Brod, Pineville (NC) Fire Department

Kerber (2011) indicates that firefighters presume that if you create enough ventilation openings that the fire will return to a fuel controlled burning regime. I am not so sure that this is the case. Until fairly recently, the concept of burning regime and influence of increased ventilation on ventilation controlled fires was not well recognized in the US fire service. However, there has been a commonly held belief that increased ventilation will improve interior conditions and reduce the potential for extreme fire behavior phenomena such as flashover. In either case, the results of the experiments conducted by UL on the influence of horizontal ventilation cast considerable doubt on the ability to accomplish either of these outcomes using horizontal, natural ventilation.

The Experiments

In order to determine the impact of increased ventilation, Kerber (2011) compared changes in temperature with varied numbers and sizes of ventilation openings. The smallest ventilation opening in the experiments conducted in both the one and two story houses was when the door on Side A was used to provide the only opening. The largest number and size of ventilation openings was in the experiments where the front door and four windows were used (see Figures 1 and 3)

The area of ventilation openings in experiments conducted in the one-story house ranged from 1.77 m2 (19.1 ft2) using the front door only to 9.51 m2 (102.4 ft2) with the front door and four windows. In the two-story house the area of ventilation openings ranged from 1.77 m2 (19.1 ft2) with front door only to 14.75 m2 (158.8 ft2) using the front door and four windows.

The most dramatic comparison is between Experiments 1 and 2 where a single opening was used (front door) and Experiments 14 and 15 where five openings were used (door and four windows).

One Story House

Experiment 1 was conducted in the one-story house using the door on Side A as the only ventilation opening. The door was opened eight minutes after ignition (480 seconds). Experiment 14 was also conducted in the one-story house, but in this case the door on Side A and four windows were used as ventilation openings. Windows in the living room and bedrooms one, two, and three were opened sequentially immediately after the door was opened, providing more than five times the ventilation area as in Experiment 1 (door only).

Figure 1. Ventilation Openings in the One-Story House

In both Experiment 1 (door only) and Experiment 14 (door and four windows), increased ventilation resulted in transition to a fully developed fire in the compartment of origin (see Figure 2). In Experiment 1, a bi-directional air track developed at the door on Side A (flames out the top and air in the bottom). In Experiment 14, a bi-directional air track is visible at all ventilation openings, with flames visible from the door and window in the Living Room on Side A and flames visible through the window in Bedroom 3. No flames extended out the ventilation openings in Bedrooms 1, 2, and 3. The upper layer in Bedroom 3 is not deep, as such there is little smoke visible exiting the window, and it appears to be serving predominantly as an inlet. On the other hand, upper layer in Bedroom 2 is considerably deeper and a large volume of thick (optically dense) smoke is pushing from the window with moderate velocity. While a bi-directional air track is evident, this window is serving predominantly as an exhaust opening.

Figure 2. Fire Conditions at 600 seconds (10:00)

As illustrated in Figure 3, increased ventilation resulted in a increase in heat release rate and subsequent increase in temperature. It is important to note that the peak temperature in Experiment 14 (door and four windows) is more than 60% higher than in Experiment 1 (door only).

Figure 3. Living Room Temperature 0.30 m(1’) Above the Floor One-Story House

Note. Adapted from Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction (p. 298), by Steve Kerber, 2011, Northbrook, IL: Underwriters Laboratories.

Based on observed conditions and temperature measurement within the one-story house, it is evident that increasing the ventilation from 1.77 m2 (19.1 ft2) using the front door to 9.51 m2 (102.4 ft2) with the front door and four windows did not return the fire to a fuel controlled burning regime and further, did not improve interior conditions.

It is important to note that these experiments were conducted without coordinated fire control operations in order to study the effects of ventilation on fire behavior. Conditions changed quickly in both experiments, but the speed with which the fire transitioned from decay to growth and reached flashover was dramatically more rapid with a larger ventilation area (i.e., door and four windows).

Two Story House

Experiment 2 was conducted in the two-story house using the door on Side A as the only ventilation opening. The door was opened ten minutes after ignition (600 seconds). Experiment 15 was also conducted in the two-story house, but in this case the door on Side A and four windows were used as ventilation openings. One window in the Living Room (Floor 1, Side A, below Bedroom 3) Den (Floor 1, Side C, below Bedroom 2) and two windows in the Family Room (Side C) were opened sequentially immediately after the door was opened, providing more than eight times the ventilation area as in Experiment 2 (door only).

Figure 4. Ventilation Openings in the Two-Story House

In both Experiment 2 (door only) and Experiment 15 (door and four windows), increased ventilation resulted in transition to a fully developed fire in the compartment of origin. Flames were seen from the family room windows in Experiment 15 (see Figure 5). However, in Experiment 2, no flames were visible on the exterior (due to the distance between the fire compartment and ventilation opening) and a bi-directional air track developed at the door on Side A (smoke out the top and air in the bottom). In Experiment 15, a bi-directional air track is visible at all ventilation openings, with flames visible from the windows in the family room on Side C. No flames extended out the ventilation openings on Side A or from the Den on Side C (see Figure 5). The upper layer is extremely deep (particularly considering the ceiling height of 16’ in the family room and foyer atrium. The velocity of smoke discharge from ventilation openings is moderate.

Figure 5. Fire Conditions at 780 seconds (13:00)

As illustrated in Figure 6, increased ventilation resulted in a increase in heat release rate and subsequent increase in temperature. It is important to note that the peak temperature in Experiment 15 (door and four windows) is approximately 50% higher than in Experiment 2 (door only).

Figure 6. Living Room Temperature 0.30 m(1’) Above the Floor One-Story House

Note. Adapted from Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction (p. 299), by Steven Kerber, 2011, Northbrook, IL: Underwriters Laboratories.

Another Consideration

Comparison of these experiments answers the questions if increased horizontal ventilation would 1) return the fire to a fuel controlled state or 2) improve interior conditions. In a word, no, increased horizontal ventilation without concurrent fire control simply increased the heat release rate (sufficient for the fire to transition through flashover to a fully developed stage) in the involved compartment.

Examining thermal conditions in other areas of the building also provides an interesting perspective on these two sets of experiments. Figure 7 illustrates temperatures at 0.91 m (3’) during Experiment 1 (door only) and Experiment 14 (door and four windows) in the one-story house.

Figure 7. Temperatures at 0.91 m (3’) during Experiments 1 and 14

Note. Adapted from Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction (p. 99, p. 162), by Steven Kerber, 2011, Northbrook, IL: Underwriters Laboratories.

Thermal conditions not only worsened in the fire compartment, but also along the flow path (for a more detailed discussion of flow path, see UL Tactical Implications Part 7) and in downstream compartments. Temperature in the hallway increased from a peak of just over 200o C to approximately 900o C when ventilation was increased by opening the four additional windows.

Unplanned Ventilation

Each of the experiments in this study were designed to examine the impact of tactical ventilation when building ventilation was limited to normal leakage and fire conditions are ventilation controlled (decay stage). In each of these experiments, increased ventilation resulted in a rapid increase in heat release rate and temperature. Even when ventilation was increased substantially (as in Experiments 14 and 15), it was not possible to return the fire to a fuel controlled burning regime.

It is also possible that a door or window will be left open by an exiting occupant or that the fire may cause window glazing to fail. The impact of these types of unplanned ventilation will have an effect on fire development. Creation of an opening prior to the fire reaching a ventilation controlled burning regime will potentially slow fire progression. However, on the flip side, providing an increased oxygen supply will allow the fire to continue to grow, potentially reaching a heat release rate that will result in flashover. If the opening is created after the fire is ventilation controlled, the results would be similar to those observed in each of these experiments. When the fire is ventilation controlled, increased ventilation results in a significant and dramatic increase in heat release rate and worsening of thermal conditions inside the building.

If the fire has self-ventilated or an opening has been created by an exiting occupant, the increased ventilation provided by creating further openings without concurrent fire control will result in a higher heat release rate than if the openings were not present and will likely result in rapid fire progression.

What’s Next?

I will be at UL the week after next and my next post will provide an update on UL’s latest research project examining the influence of vertical ventilation on fire behavior in legacy and contemporary residential construction.

Two tactical implications from the horizontal ventilation study remain to be examined in this series of posts: the impact of closed doors on tenability and the interesting question can you push fire with stream from a hoseline?

The last year has presented a challenge to maintaining frequency of posts to the CFBT Blog. However, I am renewing my commitment to post regularly and will be bringing back Reading the Fire, continuing examination of fundamental scientific concepts, and integration of fire control and ventilation tactics.

References

Kerber, S. (2011). Impact of ventilation on fire behavior in legacy and contemporary residential construction. Retrieved July 16, 2011 from http://www.ul.com/global/documents/offerings/industries/buildingmaterials/fireservice/ventilation/DHS%202008%20Grant%20Report%20Final.pdf

Influence of Ventilation in Residential Structures:
Tactical Implications Part 7

Wednesday, November 9th, 2011

The seventh tactical implication identified in the Underwriters Laboratories study of the Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction (Kerber, 2011) is the influence of changes in ventilation on flow path.

“Every new ventilation opening provides a new flow path to the fire and vice versa. This could create very dangerous conditions when there is a ventilation limited fire” (Kerber, 2011).

Air Track and Flow Path

Air track and flow path are closely related and provide an excellent framework for understanding the influence of changes in ventilation on fire development and flow path.

Air Track: Closely related to flow path, air track is the movement of air and smoke as observed from the exterior and inside the structure. Air track is used to describe a group of fire behavior indicators that includes direction of smoke movement at openings (e.g., outward, inward, pulsing), velocity and turbulence, and movement of the lower boundary of the upper layer (e.g., up, down, pulsing).

Observation of air track indicators may provide clues as to the potential flow path of air and hot gases inside the fire building. As discussed in previous posts in this series (Part 1, Part 2, Part 3, Part 4, Part 5, Part 6), movement of air to the fire has a major impact on fire development. Movement of hot gases away from the fire is equally important!

Flow Path: In a compartment fire, flow path is the course of movement hot gases between the fire and exhaust openings and the movement of air towards the fire.

Both of these components of flow path are important! Movement of hot gases between the fire an exhaust openings is a major factor in heat transfer outside the compartment of origin and presents a significant thermal threat to occupants and firefighters. When the fire is in a ventilation controlled burning regime, movement of air from to the fire provides the oxygen necessary for fire growth and increased heat release rate (impacting on conditions in the flow path downstream from the fire.

Flow path can significantly influence fire spread and the hazard presented to occupants and firefighters.

Reading the Fire

Before engaging in the meat of this UL Tactical Implication, quickly review essential air track indicators used in the Building, Smoke, Air Track, Heat, and Flame (B-SAHF) fire behavior indicators organizing scheme.

Figure 1. Air Track Indicators

As illustrated in Figure 1, key indicators include wind direction and velocity (consider this before you even arrive on-scene), directions in which the air and smoke are moving, and the velocity and flow of smoke and air movement.

Take a look at Figure 2. Consider all of the B-SAHF indicators, but pay particular attention to Air Track. What is the current flow path? How might the flow path change if one or more windows on Floor 2 Side A are opened prior to establishing fire control?

Figure 2. Residential Fire in a 1 ½ Story Wood Frame Dwelling

Photo courtesy of Curt Isakson, County Fire Tactics

UL Focus on Flow Path

Tactical implications related to flow path identified in Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction (Kerber, 2011) focus on creation of additional openings and changes in flow path as a result of “crews venting as the go” (p. 296). This is only one issue related to flow path!

The UL experiments showed that increasing the number of flow paths resulted in higher peak temperatures, a faster transition from decay to growth stage and more rapid transition to flashover. However, this is not the only hazard!

As previously discussed in the series of posts examining the fire in a Washington DC townhouse that took the lives of Firefighters Anthony Phillips and Louis Matthews, operating in the flow path presents potential for significant thermal hazard.

In this incident, the initial attack crew was operating on the first floor of a two-story townhouse with a daylight basement. When crews opened the sliding glass doors in the basement (on Side C), a flow path was created between the opening at the basement level on Side C, up an open interior stairway to the first floor, and out the first floor doorway (on Side A). Firefighters working in this flow path were subjected to extreme thermal stress, resulting in burns that took the lives of Firefighters Phillips and Mathews and serious injuries to another firefighter.

Figure 1. Perspective View of 3146 Cherry Road and Location of Slices

Note: From Simulation of the Dynamics of the Fire at 3146 Cherry Road NE Washington D.C., May 30, 1999, NISTR 6510 (p. 15) by Dan Madrzykowski and Robert Vettori, 2000, Gaithersburg, MD: National Institute for Standards and Technology.

Figure XX illustrates thermal conditions, velocity and oxygen concentration at various locations within the flow path.

Figure 10. Perspective Cutaway, Flow/Temperature, Velocity, and O2 Concentration

The temperature of the atmosphere (i.e., smoke and air) is a significant concern in the fire environment, and firefighters often wonder or speculate about how hot it was in a particular fire situation. However, gas temperature in the fire environment is a bit more complex than it might appear on the surface and is only part of the thermal hazard presented by compartment fire.

Convective heat transfer is influenced by gas temperature and velocity. When hot gases are not moving or the flow of gases across a surface (such as your body or personal protective equipment) is slow, energy is transferred from the gases to the surface (lowering the temperature of the gases, while raising surface temperature). These lower temperature gases act as an insulating layer, slowing heat transfer from higher temperature gases further away from the surface. When velocity increases, cooler gases (which have already transferred energy to the surface) move away and are replaced by higher temperature gases. When velocity increases sufficiently to result in turbulent flow, hot gases remain in contact with the surface on a relatively constant basis, increasing convective heat flux.

For a more detailed discussion of this incident and the influence of radiative and convective heat transfer in the flow path, see the prior posts on the Washington DC Townhouse Fire Case Study.

Wind Driven Fires & Flow Path

While operating in the flow path presents serious risk, when fire behavior is influenced by wind, conditions in the flow path can be even more severe. In experiments conducted by the National Institute of Standards and Technology (NIST) demonstrated that under wind driven conditions, both temperature and heat flux, which were twice as high in the “flow” portion of the corridor as opposed to the “static” portion of the corridor (where there was no flow path). See the previous posts on Wind Driven Fires for more information on flow path hazards under wind driven conditions:

Discussion

The sixth and seventh tactical implications identified in the UL Horizontal Ventilation Study are interrelated and can be expanded to include the following key points:

  • Heat transfer (convective and radiative) is greatest along the flow path between the fire and exhaust opening.
  • Exhaust openings located higher than the fire will increase the velocity of gases along the flow path (further increasing convective heat transfer).
  • Flow of hot gases from the fire to an exhaust opening is significantly influenced by air flow from inlet openings to the fire (the greater the inflow of air, the higher the heat release rate and flow of hot gases to the exhaust opening).
  • Flow path can be created by a single opening that serves as both inlet and exhaust (such as an open door or window).
  • Thermal conditions in the flow path can quickly become untenable for both civilian occupants and firefighters. As noted in an earlier NIST Study examining wind driven fires, under wind driven conditions this change can be extremely rapid.
  • Closing an inlet, exhaust opening, or introducing a barrier (such as a closed door) in the flow path slows gas flow and reduces the hazard downstream from the barrier.
  • When the fire is ventilation controlled, limiting inflow of air (e.g., door control) can slow the increase in heat release rate and progression to a growth stage fire.
  • Multiple openings results in multiple flow paths and increased air flow to the fire, resulting in more rapid fire development and increased heat release rate.

What’s Next?

The next tactical implication identified in the UL Horizontal Ventilation study examines an interesting question: Can you vent enough (to return the fire to a fuel controlled burning regime)? This question may also be restated as can you perform sufficient natural horizontal ventilation to improve internal conditions. The answer to this question will likely be extended through the Vertical Ventilation Study that will be conducted by UL in early 2012!

References

District of Columbia (DC) Fire & EMS. (2000). Report from the reconstruction committee: Fire at 3146 Cherry Road NE, Washington DC, May 30, 1999. Washington, DC: Author.

Kerber, S. (2011). Impact of ventilation on fire behavior in legacy and contemporary residential construction. Retrieved July 16, 2011 from http://www.ul.com/global/documents/offerings/industries/buildingmaterials/fireservice/ventilation/DHS%202008%20Grant%20Report%20Final.pdf

Madrzykowski, D. & Kerber, S. (2009). Fire Fighting Tactics Under Wind Driven Conditions. Retrieved (in four parts) February 28, 2009 from http://www.nfpa.org/assets/files//PDF/Research/Wind_Driven_Report_Part1.pdf; http://www.nfpa.org/assets/files//PDF/Research/Wind_Driven_Report_Part2.pdf;http://www.nfpa.org/assets/files//PDF/Research/Wind_Driven_Report_Part3.pdf;http://www.nfpa.org/assets/files//PDF/Research/Wind_Driven_Report_Part4.pdf.

Madrzykowski, D. & Vettori, R. (2000). Simulation of the Dynamics of the Fire at 3146 Cherry Road NE Washington D.C., May 30, 1999, NISTR 6510. August 31, 2009 from http://fire.nist.gov/CDPUBS/NISTIR_6510/6510c.pdf

National Institute for Occupational Safety and Health (NIOSH). (1999). Death in the line of duty, Report 99-21. Retrieved August 31, 2009 from http://www.cdc.gov/niosh/fire/reports/face9921.html

 

Influence of Ventilation in Residential Structures: Tactical Implications Part 5

Thursday, September 8th, 2011

The fifth tactical implication identified in the Underwriters Laboratories study of the Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction (Kerber, 2011) is described as failure of the smoke layer to lift following horizontal natural ventilation and smoke tunneling and rapid air movement in through the front door.

In the experiments conducted by UL, both the single and two story dwellings filled rapidly with smoke with the smoke layer reaching the floor prior to ventilation. This resulted in zero visibility throughout the interior (with the exception of the one bedroom with a closed door). After ventilation, the smoke layer did not lift (as many firefighters might anticipate) as the rapid inward movement of air simply produced a tunnel of clear space just inside the doorway.

Put in the context of the Building, Smoke, Air Track, Heat, and Flame (B-SAHF) fire behavior indicators, these phenomena fit in the categories of smoke and air track. Why did these phenomena occur and what can firefighters infer based on observation of these fire behavior indicators?

Smoke Versus Air Track

There are a number of interrelationships between Smoke and Air Track. However, in the B-SAHF organizing scheme they are considered separately. As we begin to develop or refine the map of Smoke Indicators it is useful to revisit the difference between these two categories in the B-SAHF scheme.

Smoke: What does the smoke look like and where is it coming from? This indicator can be extremely useful in determining the location and extent of the fire. Smoke indicators may be visible on the exterior as well as inside the building. Don’t forget that size-up and dynamic risk assessment must continue after you have made entry!

Air Track: Related to smoke, air track is the movement of both smoke (generally out from the fire area) and air (generally in towards the fire area). Observation of air track starts from the exterior but becomes more critical when making entry. What does the air track look like at the door? Air track continues to be significant when you are working on the interior.

Smoke Indicators

There are a number of smoke characteristics and observations that provide important indications of current and potential fire behavior. These include:

  • Location: Where can you see smoke (exterior and interior)?
  • Optical Density (Thickness): How dense is the smoke? Can you see through it? Does it appear to have texture like velvet (indicating high particulate content)?
  • Color: What color is the smoke? Don’t read too much into this, but consider color in context with the other indicators.
  • Physical Density (Buoyancy): Is the smoke rising, sinking, or staying at the same level?
  • Thickness of the Upper Layer: How thick is the upper layer (distance from the ceiling to the bottom of the hot gas layer)?

As discussed in Reading the Fire: Smoke Indicators Part 2, these indicators can be displayed in a concept map to show greater detail and their interrelationships (Figure 1).

Figure 1. Smoke Indicators Concept Map

Air Track

Air track includes factors related to the movement of smoke out of the compartment or building and the movement of air into the fire. Air track is caused by pressure differentials inside and outside the compartment and by gravity current (differences in density between the hot smoke and cooler air). Air track indicators include velocity, turbulence, direction, and movement of the hot gas layer.

  • Direction: What direction is the smoke and air moving at specific openings? Is it moving in, out, both directions (bi-directional), or is it pulsing in and out?
  • Wind: What is the wind direction and velocity? Wind is a critical indicator as it can mask other smoke and air track indicators as well as serving as a potentially hazardous influence on fire behavior (particularly when the fire is in a ventilation controlled burning regime).
  • Velocity & Flow: High velocity, turbulent smoke discharge is indicative of high temperature. However, it is essential to consider the size of the opening as velocity is determined by the area of the discharge opening and the pressure. Velocity of air is also an important indicator. Under ventilation controlled conditions, rapid intake of air will be followed by a significant increase in heat release rate.

As discussed in Reading the Fire: Air Track Indicators Part 2, these indicators can be displayed in a concept map to show greater detail and their interrelationships (Figure 2).

Figure 2. Air Track Indicators Concept Map

air t

Discharge of smoke at openings and potential openings (Building Factors) is likely the most obvious indicator of air track while lack of smoke discharge may be a less obvious, but equally important sign of inward movement of air. Observation and interpretation of smoke and air movement at openings is an essential part of air track assessment, but it must not stop there. Movement of smoke and air on the interior can also provide important information regarding fire behavior.

An Ongoing Process

Reading the fire is an ongoing process, beginning with reading the buildings in your response area prior to the incident and continuing throughout firefighting operations. It is essential to not only recognize key indicators, but to also note changing conditions. This can be difficult when firefighters and officer are focused on the task at hand.

UL Experiment 13

This experiment examined the impact of horizontal ventilation through the door on Side A and one window as high as possible on Side C near the seat of the fire. The family room was the fire compartment. This room had a high (two-story) ceiling with windows at ground level and the second floor level (see Figure 3).

Figure 3. Two-Story Dwelling

In this experiment, the fire was allowed to progress for 10:00 after ignition, at which point the front door (see Figure 3) was opened to simulate firefighters making entry. Fifteen seconds after the front door was opened (10:15), an upper window in the family room (see Figure 3) was opened. No suppression action was taken until 12:28, at which point a 10 second application of water was made through the window on Side C using a straight stream from a combination nozzle.

As with all the other experiments in this series fire development followed a consistent path. The fire quickly consumed much of the available oxygen inside the building and became ventilation controlled. At oxygen concentration was reduced, heat release rate and temperature within the building also dropped. Concurrently, smoke and air track indicators visible from the exterior were diminished. Just prior to opening the door on Side A, there was little visible smoke from the structure (see Figure 4).

Figure 4. Experiment 13 at 00:09:56 (Prior to Ventilation)

As illustrated in Figure 5, a bi-directional air track was created when the front door was opened. Hot smoke flowed out the upper area of the doorway while air pushed in the bottom creating a tunnel of clear space inside the doorway (but no generalized lifting of the upper layer.

Figure 5. Experiment 13 at 00:10:14 (Door Open)

As illustrated in Figure 6, opening the upper level window in the family room resulted in a unidirectional air track flowing from the front door to the upper level window in the family room. No significant exhaust of smoke can be seen at the front door, while a large volume of smoke is exiting the window. However, while the tunneling effect at floor level was more pronounced (visibility extended from the front door to the family room), there was no generalized lifting of the upper layer throughout the remainder of the building.

Figure 6. Experiment 13 at 00:10:21 (Door and Window Open)

With the increased air flow provided by ventilation through the door on Side A and Window at the upper level on Side C, the fire quickly transitioned to a fully developed stage in the family room. The heat release rate (HRR) and smoke production quickly exceeded the limited ventilation provided by these two openings and the air track at the front door returned to bi-directional (smoke out at the upper level and air in at the lower level) as shown in Figure 7.

Figure 7. Experiment 13 at 00:11:22 (Door and Window Open)

What is the significance of this observation? Movement of smoke out the door (likely the entry point for firefighters entering for fire attack, search, and other interior operations) points to significant potential for flame spread through the upper layer towards this opening. The temperature of the upper layer is hot, but flame temperature is even higher, increasing the radiant heat flux (transfer) to crews working below. Flame spread towards the entry point also has the potential to trap, and injure firefighters working inside.

Gas Velocity and Air Track

A great deal can be learned by examining both the visual indicators illustrated in Figures 4-7 and measurements taken of gas velocity at the front door. During the ventilation experiments conducted by UL, gas velocities were measured at the front door and at the window used for ventilation (see Figure 3). Five bidirectional probes were placed in the doorway at 0.33 m (1’) intervals. Positive values show gas movement out of the building while negative values show inward gas movement. In order to provide a simplified view of gas movement at the doorway, Figure 8 illustrates gas velocity 0.33 m (1’) below the top of the door, 0.33 m (1’) from the bottom of the door, and 0.66 m (2’) above the bottom of the door.

A bidirectional (out at the top and in at the bottom) air track developed at the doorway before the door was opened (see Figure 8) as a result of leakage at this opening. It is interesting to note variations in the velocity of inward movement of air from the exterior of the building, likely a result of changes in combustion as the fire became ventilation controlled. The outward flow at the upper level resulted in visible smoke on the exterior of the building. While not visible, inward movement of air was also occurring (as shown by measurement of gas velocity at lower levels in the doorway.

Creation of the initial ventilation opening by opening the front door created a strong bidirectional air track with smoke pushing out the top of the door while air rapidly moved in the bottom. Had the door remained the only ventilation opening, this bidirectional flow would have been sustained (as it was in all experiments where the door was the only ventilation opening).

Opening the upper window in the family room resulted in a unidirectional flow inward through the doorway. However, this phenomenon was short lived, with the bidirectional flow reoccurring in less than 60 seconds. This change in air track resulted from increased heat release rate as additional air supply was provided to the fire in the family room.

Figure 8. Front Door Velocities

Note: Adapted from Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction (p. 243), by Stephen Kerber, Northbrook, IL: Underwriters Laboratories, 2011.

While not the central focus of the UL research, these experiments also examined the effects of exterior fire stream application on fire conditions and tenability. Each experiment included a 10 second application with a straight stream and a 10 second application of a 30o fog pattern. Between these two applications, fire growth was allowed to resume for approximately 60 seconds.

The straight stream application resulted in a reduction of temperature in the fire compartment and adjacent compartments (where there was an opening to the family room or hallway) as water applied through the upper window on Side C (ventilation opening) cooled the compartment linings (ceiling and opposite wall) and water deflected off the ceiling dropped onto the burning fuel. As the stream was applied, air track at the door on Side A changed from bidirectional to unidirectional (inward). This is likely due to the reduction of heat release rate achieved by application of water onto the burning fuel with limited steam production.

When the fog pattern was applied, there was also a reduction of temperature in the fire compartment and adjacent compartments (where there was an opening in the family room or hallway) as water was applied through the upper window on Side C (ventilation opening) cooled the upper layer, compartment linings, and water deflected off the ceiling dropped onto the burning fuel. The only interconnected area that showed a brief increase in temperature was the ceiling level in the dining room. However, lower levels in this room showed an appreciable drop in temperature. Air track at the door on Side A changed from bidirectional to unidirectional (outward) when the fog stream was applied. This effect is likely due to air movement inward at the window on Side C and the larger volume of steam produced on contact with compartment linings as a result of the larger surface area of the fog stream.

The effect of exterior streams will be examined in more detail in a subsequent post.

Important Lessons

The fifth tactical implication identified in the Underwriters Laboratories study of the Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction (Kerber, 2011) is described as failure of the smoke layer to lift following horizontal natural ventilation and smoke tunneling and rapid air movement in through the front door.

Additional lessons that can be learned from this experiment include:

  • Ventilating horizontally at a high point results in higher flow of both air and smoke.
  • Increased inward air flow results in a rapid increase in heat release rate.
  • The rate of fire growth quickly outpaced the capability of the desired exhaust opening, returning the intended inlet to a bi-directional air track (potentially placing firefighters entering for fire attack or search at risk due to rapid fire spread towards their entry point).

Tactical applications of this information include:

  • Ensure that the attack team is in place with a charged line and ready to (or has already) attack the fire (not simply ready to enter the building) before initiating horizontal ventilation.
  • Cool the upper layer any time that it is above 100o C (212o F) to reduce radiant and convective heat flux and to limit potential for ignition and flaming combustion in the upper layer.

Note that this research project did not examine the impact of gas cooling, but examination of the temperatures at the upper levels in this experiment (and others in this series) point to the need to cool hot gases overhead.

What’s Next?

I am on the hunt for videos that will allow readers to apply the tactical implications of the UL study that have been examined to this point in conjunction with the B-SAHF fire behavior indicators. My next post will likely provide an expanded series of exercises in Reading the Fire.

The next tactical implication identified in the UL study (Kerber, 2011) examines the hazards encountered during Vent Enter Search (VES) tactical operations. A subsequent post will examine this tactic in some detail and explore this tactical implication in greater depth.

References

Kerber, S. (2011). Impact of ventilation on fire behavior in legacy and contemporary residential construction. Retrieved July 16, 2011 from http://www.ul.com/global/documents/offerings/industries/buildingmaterials/fireservice/ventilation/DHS%202008%20Grant%20Report%20Final.pdf

Influence of Ventilation in Residential Structures: Tactical Implications Part 4

Sunday, August 14th, 2011

The fourth tactical implication identified in the Underwriters Laboratories study of the Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction (Kerber, 2011) is that fire attack and (tactical) ventilation must be coordinated. This recommendation has been repeated in National Institute for Occupational Safety and Health (NIOSH) Death in the Line of Duty Reports for many years. In fact, most reports on firefighter fatalities related to rapid fire progression contain this recommendation.

Importance of Coordination

Coordination of (tactical) ventilation and fire attack as a tactical implication is closely related to the first two tactical implications identified in the UL study; potential changes in fire behavior based on stages of fire development, burning regime, and changes in ventilation profile that increase oxygen supplied to the fire.

If air is added to the fire and water is not applied in the appropriate time frame the fire gets larger and the hazards to firefighters increase. Examining the times to untenability provides the best case scenario of how coordinated the attack needs to be. Taking the average time for every experiment from the time of ventilation to the time of the onset of firefighter untenability conditions yields 100 seconds for the one-story house and 200 seconds for the two-story house. In many of the experiments from the onset of firefighter untenability until flashover was less than 10 seconds. These times should be treated as very conservative. If a vent location already exists because the homeowner left a window or door open then the fire is going to respond faster to additional ventilation openings because the temperatures in the house are going to be higher at the time of the additional openings (Kerber, 2011, p. 289-290)

The Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction Underwriters Laboratories (UL) on-line course and report provide an example of firefighters are at risk when ventilation is performed prior to entry, fire attack is delayed, and other tactical operations such as primary search are initiated.

In UL’s hypothetical example, the firefighters make entry into the one-story house, search the living room (fire compartment), the kitchen, and dining room shortly after forcing the door and ventilating a large window in the fire compartment. Consider a somewhat different scenario, with the same fire conditions.

Companies respond to a residential fire with persons reported during the early morning hours. A truck and engine arrive almost simultaneously and while the engine lays a supply line from a nearby hydrant, the truck company forces entry, ventilates a window on Side A, and begins primary search (anticipating that the engine crew will be right behind them to attack the fire). The engine completes a forward lay and begins to stretch an attack line after the search team has made entry.

Figure 1. Timeline and Progression of Primary Search

Figure 2. View of the Living Room (Fire Compartment) from the Door on Side A

As illustrated in Figure 3, visible flaming combustion when the door is opened at 08:00 is limited to a small flame from the top of the couch just inside the door on Side A. However, in the 30 seconds that it takes for the search team to make entry, flaming combustion has resumed and flames are near or at the ceiling above the couch. The search team may estimate that they have time to complete a quick search of the bedrooms (likely location of the reported persons). However, fire development progresses to untenable conditions within a minute, trapping the crew on Side D of the house.

Figure 3. Fire Progression in the Living Room 00:08:00 to 00:10:00

As the search team completes primary search of Bedroom 2 and moves towards Bedroom 3 in the hallway, conditions have deteriorated to an untenable level. Figure 4 illustrates the change in temperature at the 3’ level in the Living Room (fire compartment). Shortly before the search team reached Bedroom 2, fire conditions in the living room began to change dramatically, with temperature at the 3’ level transitioning from ordinary to extreme, quickly becoming untenable in the living room, hallway and adjacent compartments. In addition to this significant change in temperature, flames (with temperatures higher than the gas temperature at the 3’ level) significantly increase radiant heat transfer (flux) to the surface of both fuel packages and firefighters protective equipment.

Figure 4. Temperature at the 3’ Level

Note: Figure 4 illustrates temperature conditions starting eight minutes after ignition. The fire previously progressed through incipient and growth stages before beginning to decay due to lack of ventilation.

Why the Dramatic Change in Conditions?

As discussed in UL Tactical Implications Part 1, Fires in the contemporary environment progress from ignition and incipient stage to growth, but often become ventilation controlled and begin to decay, rather than continuing to grow into a fully developed fire. This ventilation induced decay continues until the ventilation profile changes (e.g., window failure due to fire effects, opening a door for entry or egress, or intentional creation of ventilation openings by firefighters. When ventilation is increased, heat release rate again rises and temperature climbs with the fire potentially transitioning through flashover to the fully developed stage (see Figure 4 and 5).

Figure 5. Fire Development in a Compartment

Captain James Mendoza of the San Jose (CA) Fire Department and CFBT-US Lead Instructor demonstrates the influence of ventilation on fire development using a small scale prop developed by Dr. Stefan Svensson of the Swedish Civil Contingencies Agency.

The prop used in this demonstration is a small, single compartment with a limited ventilation opening on the right side (which in a full size building could be represented by normal building leakage or a compartment opening that is restricted such as a partially open door or window). The front wall of the prop is ceramic glass to permit direct observation of fire conditions within the compartment.

As you watch this demonstration, pay particular attention to how conditions change as the fire develops and then enters the decay stage. In addition, observe how quickly the fire returns to the growth stage and develops conditions that would be untenable after the window is opened at 12:17.

Download Doll’s House Plans (or Doll’s House Plans: Metric) for directions on how to construct a similar small scale prop.

Fire development and changes in conditions following ventilation in this demonstration mirror those seen in the full scale experiments conducted by UL. Increasing ventilation to a ventilation controlled fire, results in increased heat release rate and transition from decay to the growth stage of fire development.

The same phenomena can be observed under fireground conditions in the following video clip of a residential fire in Dolton, Illinois (this is a long video, watch the first several minutes to observe the changes in fire behavior).

It appears that the front door was open at the start of the video clip and the large picture window on Side A was ventilated at approximately 00:47. Fire conditions quickly transition to the growth stage with flames exiting the window and door, causing firefighters on an uncharged hoseline that had been advanced into Floor 1, to quickly withdraw.

As discussed in UL Tactical Implications: Part 1:

  • Fires that have progressed beyond the incipient stage are likely to be ventilation controlled when the fire department arrives.
  • Ventilation controlled fires may be in the growth, decay, or fully developed stage.
  • Regardless of the stage of fire development, when a fire is ventilation controlled, increased ventilation will always result in increased HRR.
  • Firefighters and fire officers must recognize that the ventilation profile can change (e.g., increasing ventilation) as a result of tactical action or fire effects on the building (e.g., window failure).
  • Firefighters and fire officers must anticipate potential changes in fire behavior related to changes in the ventilation profile and ensure that fire attack and ventilation are closely coordinated.

Coordinated Tactical Operations

Understanding how fire behavior can be influenced by changes in ventilation is essential. But how can firefighters put this knowledge to use on the fireground and what exactly does coordination of tactical ventilation and fire attack really mean?

Tactical ventilation can be defined as the planned, systematic, and coordinated removal of hot smoke and fire gases and their replacement with fresh air. Each of the elements of this definition is important to safe and effective tactical operations.

Ventilation (both tactical and unplanned) not only removes hot smoke, but it also introduces fresh air which can have a significant effect on fire behavior.

Tactical ventilation must be planned; these two elements speak to the intentional nature of tactical ventilation. Tactics to change the ventilation profile must be intended to influence the fire environment or fire behavior in some way (e.g., raise the level of the upper layer to increase visibility and tenability). The ventilation plan must also consider the flow path (e.g., vent ahead of, not behind, the attack team; vent in the immediate area of the fire, not at a remote location).

Tactical ventilation must be systematic, exhaust openings should generally be made before inlet openings (particularly when working with positive pressure ventilation or when taking advantage of wind effects).

And as pointed out in the UL Study (Kerber, 2011), tactical ventilation must be coordinated. Coordination of ventilation and other tactical operations requires consideration of sequence and timing:

Sequence: Ventilation may be completed before, during, or after fire attack has been initiated. Sequence will likely depend on the stage of fire development, burning regime, time required to reach the fire.

If the fire is small and staffing is limited, it may be appropriate to control the fire and then effect ventilation (e.g., hydraulic ventilation performed by the attack team). This approach minimizes potential fire growth,

In general, when the fire is ventilation controlled (as those beyond the incipient stage are likely to be), ventilation should not be completed unless the attack line(s) can quickly apply water to the seat of the fire. In a small, single family dwelling this may mean that the attack team is on-air, the line is charged, and the entry door is unlocked or has been forced and is being controlled (held closed). In a larger building, this may mean that the attack line has entered the structure and is in position to move onto the fire floor or into the fire area.

The key questions that must be answered prior to implementing tactical ventilation are:

  1. What influence will these ventilation tactics have on fire behavior?
  2. Are charged and staffed attack line(s) in place?
  3. Will the attack team(s) be able to quickly reach the fire?
  4. How will this impact crews operating on the interior of the building?

Coordination requires clear, direct communication between companies or crews assigned to ventilation, fire attack, and other tactical functions that are or will be taking place inside the building.

Important: While not a tactical implication directly raised by the UL study, another important consideration is the hazard of working without or ahead of the hoseline. While a controversial topic in the US fire service (where truck company personnel generally work on the interior without a hoseline), searching with a hoseline provides a means of protection and a defined exit path. Staffing is another key element of the operational context. If you do not have enough personnel to control the fire and search; in most cases it is likely the best course of action to control the fire and ensure a safer operating environment for search operations.

What’s Next?

The next tactical implication identified in the UL study (Kerber, 2011) examines information that may be obtained by reading the air track at the entry point opening. This implication will be expanded with a broader discussion of air track indicators and how related hazards can be mitigated to improve firefighter safety.

References

Kerber, S. (2011). Impact of ventilation on fire behavior in legacy and contemporary residential construction. Retrieved July 16, 2011 from http://www.ul.com/global/documents/offerings/industries/buildingmaterials/fireservice/ventilation/DHS%202008%20Grant%20Report%20Final.pdf

 

Note: Figure 4 illustrates temperature conditions starting eight minutes after ignition. The fire previously progressed through incipient and growth stages before beginning to decay due to lack of ventilation.

Why the Dramatic Change in Conditions?

As discussed in UL Tactical Implications Part 1 [LINK], Fires in the contemporary environment progress from ignition and incipient stage to growth, but often become ventilation controlled and begin to decay, rather than continuing to grow into a fully developed fire. This ventilation induced decay continues until the ventilation profile changes (e.g., window failure due to fire effects, opening a door for entry or egress, or intentional creation of ventilation openings by firefighters. When ventilation is increased, heat release rate again rises and temperature climbs with the fire potentially transitioning through flashover to the fully developed stage (see Figure 4 and 5).

Figure 5. Fire Development in a Compartment

Reading the Fire 15

Sunday, July 24th, 2011

Developing and maintaining proficiency in reading the Fire using the B-SAHF (Building, Smoke, Air Track, Heat, and Flame) organizing scheme for fire behavior indicators, requires practice. This post provides an opportunity to exercise your skills using a video segment shot during a commercial fire.

Residential Fire

This post examines fire development during a residential fire in New Chicago, Indiana.

Download and the B-SAHF Worksheet.

Watch the first 30 seconds (0:30) of the video. First, describe what you observe in terms of the Building, Smoke, Air Track, Heat, and Flame Indicators; then answer the following five standard questions?

  1. What additional information would you like to have? How could you obtain it?
  2. What stage(s) of development is the fire likely to be in (incipient, growth, fully developed, or decay)?
  3. What burning regime is the fire in (fuel controlled or ventilation controlled)?
  4. What conditions would you expect to find inside this building?
  5. How would you expect the fire to develop over the next two to three minutes

In addition, consider how the answers to these questions impact your assessment of the potential for survival of possible occupants.

Now watch the video clip from 0:30 until firefighters make entry at 3:05. Now answer the following questions:

  1. Did fire conditions progress as you anticipated?
  2. What changes in the B-SAHF indicators did you observe?
  3. How do you think that the stage(s) of fire development and burning regime will change over the next few minutes?
  4. What conditions would you expect to find inside this building now?
  5. How would you expect the fire to develop over the next two to three minutes

The crews working in this video appeared to achieve fire control fairly quickly and without incident. However, consider the following tactical and task related questions:

  1. It did not appear that any member of the first arriving companies performed a 360o recon and size-up (they may have, but this was not visible in the video). Why might this be a critical step in size-up at a residential fire?
  2. It appeared that two lines were run simultaneously (the first line to the door ended up as the back-up line, possibly due to a slight delay in charging the line). How should fire attack and backup roles be coordinated?
  3. Fire attack was initiated from the interior (unburned side). What would have been the impact of the first line darkening the fire from the exterior (prior to entry)?
  4. Were there any indicators of potential collapse (partial) of the roof? How would you manage this risk when working in a lightweight wood frame residence with observed extension into the trussloft? What factors would influence your decision-making and actions?

Reading the Fire

See the following posts for more information on reading the fire:

Ed Hartin, MS, EFO, MIFireE, CFO

Influence of Ventilation in Residential Structures: Tactical Implications Part 3

Sunday, July 17th, 2011

UL’s third tactical implication is that there may be little smoke showing when a fire initially enters the decay stage as a result of limited ventilation. These fire conditions may present similar indicators to an incipient fire. However, fire conditions and the hazards presented to firefighters are considerably different.

Visible Indications of Fire Development

In Reading the Fire: B-SAHF, I introduced Building, Smoke, Air Track, Heat, and Flame (B-SAHF) as an organizing scheme for fire behavior indicators. Use of a standardized and organized approach to reading the fire can improve our ability to assess current fire conditions and predict likely fire development and changes that may occur.

Station Officer Shan Raffel of Queensland (Australia) Fire Rescue recently published an excellent article titled The Art of Reading Fire on the FirefighterNation website that provides another view of the B-SAHF indicators and Reading the Fire.

Building factors (particularly the normal ventilation profile, size and compartmentation, and thermal characteristics) can have a significant impact on fire development and how fire conditions present from the exterior of the building. However, this UL tactical implication relates most closely to Smoke and Air Track as well as somewhat indirectly to Heat (but this is the key to understanding what is happening). First a quick review of these key indicators

Smoke: What does the smoke look like and where is it coming from? This indicator can be extremely useful in determining the location and extent of the fire. Smoke indicators may be visible on the exterior as well as inside the building.

Air Track: Related to smoke, air track is the movement of both smoke (generally out from the fire area) and air (generally in towards the fire area).

Heat: This includes a number of indirect indicators. Heat cannot be observed directly, but you can feel changes in temperature and may observe the effects of heat on the building and its contents. Visual clues such as crazing of glass and visible pyrolysis from fuel that has not yet ignited are also useful heat related indicators. Important: Temperature influences smoke and air track indicators such as volume and velocity of smoke discharge.

For a more detailed look at B-SAHF and reading the fire, see the following posts:

How to Improve Your Skills
Building Factors
Building Factors Part 2
Building Factors Part 3
Smoke Indicators
Smoke Indicators Part 2
Air Track Indicators
Air Track Indicators Part 2
Heat Indicators
Heat Indicators Part 2
Heat Indicators Part 3
Flame Indicators
Flame Indicators Part 2
Incipient Stage Fires: Key Fire Behavior Indicators
Growth Stage Fires: Key Fire Behavior Indicators
Fully Developed Fires: Key Fire Behavior Indicators
Decay Stage Fires: Key Fire Behavior Indicators

Stages of Fire Development, Burning Regime, Smoke, Air Track & Heat

While the “stages of fire” have been described differently in fire service textbooks the phenomenon of fire development is the same. For our purposes, the stages of fire development in a compartment will be described as incipient, growth, fully developed and decay (see Figure 1). Despite dividing fire development into four “stages” the actual process is continuous with “stages” flowing from one to the next. While it may be possible to clearly define these transitions in the laboratory, in the field it is often difficult to tell when one ends and the next begins.

Understanding the stages of fire development is important, but this only provides a limited picture of fire development in a compartment. Conversion of chemical potential energy from fuel depends on availability of adequate oxygen for the combustion reaction to occur. As the ambient air in the compartment provides adequate oxygen, in incipient stage and early growth stage, heat release rate is limited by the chemical and physical characteristics of the fuel. This condition is known as a fuel controlled burning regime. In a compartment fire, combustion occurs in an enclosure where the air available for combustion is limited by 1) the volume of the compartment and 2) ventilation. Ventilation in a compartment fire is limited (particularly if doors and windows are closed and intact), as the fire grows and heat release rate increases, so too does demand for oxygen. When fire growth is limited by the available oxygen, heat release rate is slowed and then diminishes. This condition is known as a ventilation controlled burning regime.

Many if not most fires that have progressed beyond the incipient stage when the fire department arrives are ventilation controlled. This means that the heat release rate (the fire’s power) is limited by the existing ventilation. If ventilation is increased, either through tactical action or unplanned ventilation resulting from effects of the fire (e.g., failure of a window) or human action (e.g., exiting civilians leaving a door open), heat release rate will increase (see Figure 1)

Figure 1. Fire Development Curve (Fuel and Ventilation Controlled Regimes)

Several things happen as a compartment fire develops: Heat release rate increases, smoke production increases, and pressure within the compartment increases proportionally to the absolute temperature. These conditions result in a number of fire behavior indicators that may be visible from the exterior of the building. As a fire moves from the Incipient to the Growth Stage, an increasing volume of smoke may be visible from the exterior (Smoke Indicator) and the velocity of smoke discharge will likely increase (Air Track Indicator and indirect Heat Indicator).

It is a reasonably logical conclusion that a smaller volume of smoke and lower velocity of smoke discharge will be observed in incipient and early growth stage fires and the volume and velocity of smoke discharge will increase as the fire develops. However, what happens when the fire becomes ventilation controlled?

Influence of Ventilation on Residential Fire Behavior

Earlier this year, Underwriters Laboratories (UL) conducted a series of full-scale experiments to determine the influence of ventilation on fire behavior in legacy and contemporary residential construction (see Did You Ever Wonder? and UL Ventilation Course).

These tests were conducted in full-scale one and two-story, wood-frame structures constructed inside the UL laboratory in Northbrook, IL. Fires in the one-story structure were all started in the living room (see Figure 2) and involved typical contents found in a single-family home.

Figure 2: One-Story Structure and Floor Plan

As discussed in UL Tactical Implications Part 1 and Part 2, each of the fires during these tests quickly became ventilation controlled due to the fuel load within the buildings and limited ventilation provided by closed and intact doors and windows.

As each fire developed, the volume of smoke visible from the exterior and velocity of smoke discharge increased. This is consistent with fire development within the structure and increasing heat release rate, temperature, and volume of smoke production from the developing fire. Figure 3 illustrates exterior conditions at 05:05 during Test 5 conducted in the one-story residence.

Figure 3: Conditions at 05:05 (UL Test 5)

Interestingly, as the fire became ventilation controlled (as determined by both measurement of oxygen concentration and the heat release rate in the building), the volume and velocity of smoke discharge decreased to a negligible level as illustrated in Figure 4.

Figure 4: Conditions at 05:34 (UL Test 5)

This change occurred within a matter of 30 seconds! How might this influence firefighters’ perception of fire conditions inside the building if they arrived at 05:34 rather than 05:04? While presenting much the same as an incipient or early growth stage fire, conditions within the building at 05:34 are significantly ventilation controlled and increased ventilation resulted in rapid fire development and transition through flashover to a fully developed fire.

NIST Phoenix Warehouse Tests

In the Hazard of Ventilation Controlled Fires, I discussed a series of tests conducted by the National Institute for Standards and Technology (NIST) at an ordinary constructed warehouse in Phoenix, AZ. These tests were intended to develop information about performance of ordinary constructed buildings related to structural collapse. However, they also provided some interesting information regarding fire behavior.

One of the tests involved a fire in the front section of the warehouse that measured 50’ x 90’ (15.2 m x 27.4 m) with a height of 15’ (4.6 m) to the top of the pitched truss roof. The fuel load for this test included four stacks of 10 wood pallets and the interior finish and combustible structural elements of the building.  All doors and windows were closed at the start of the test.

Figure 5 illustrates a large volume of dark gray to black smoke discharging from the roof of the structure and flames visible from roof ventilators at 03:57. The B-SAHF indicators visible n this photo indicate a significant growth stage fire within this building.

Figure 5. Conditions at 03:57 (NIST Warehouse Test)

However, at 05:31 conditions visible on the exterior are quite different. The color and volume of smoke discharge (Smoke Indicators) as well as the velocity of discharge (Air Track Indicator) may lead firefighters to believe that this is an incipient or early growth stage fire. Nothing could be further from the truth. This fire is in the decay stage as a result of limited ventilation and any increase in ventilation will result in a rapid and significant increase in heat release rate!

Figure 6. Conditions at 05:31 (NIST Warehouse Test)

For more information on these tests see Structural Collapse Fire Tests: Single Story, Ordinary Construction Warehouse (Stroup, Madrzykowski, Walton, & Twilley, 2003) or view the videos of this series of tests at the NIST Structural Collapse webpage.

The Key

Heat release rate and temperature drop as the fire becomes ventilation controlled. Volume and velocity of smoke discharge are a function of pressure (given a constant opening size). Reduction in temperature and corresponding reduction in pressure will result in a smaller volume and lower velocity of smoke discharge.

When the temperature is the same, the velocity of discharge will likely be similar. Figure 1 shows that the temperature inside a compartment may be the same during the growth and decay stages of the fire. If the ventilation profile (number, size, and location of openings) remains the same, similar Smoke and Air Track indicators can be present.

Decay stage incidators may be subtle. Consider the full range of B-SAHF inciators that may be observed under ventilation controlled, decay stage conditions (see Figure 7.

Figure 7. B-SAHF Decay Stage Indicators.

Durango, Colorado Commercial Fire

CFBT-US developed a case study examining an extreme fire behavior event that occurred during a commercial fire in Durango, CO in 2008 injuring nine firefighters and fire officers. The reporting party indicated that there was a large amount of dark smoke coming from the roof of the building. However, when firefighters arrived, they found nothing showing but a small amount of light colored smoke. Why might this have been the case?

Download a copy of the Fire Behavior Case Study: Durango CO Commercial Fire and see if this may have been a result of similar fire development and presentation of fire behavior indicators as seen in the UL and NIST tests!

Ed Hartin, MS, EFO, MIFireE, CFO

References

Kerber, S. (2011). Impact of ventilation on fire behavior in legacy and contemporary residential construction. Retrieved July 16, 2011 from http://www.ul.com/global/documents/offerings/industries/buildingmaterials/fireservice/ventilation/DHS%202008%20Grant%20Report%20Final.pdf.

Stroup, D., Madrzykowski, D., Walton, W., & Twilley, W. (2003). Structural collapse fire tests: Single story, ordinary construction warehouse, NISTIR 6959. Retrieved July 16, 2011 from http://www.nist.gov/customcf/get_pdf.cfm?pub_id=861215

Flashover!

Monday, January 3rd, 2011

There were multiple near miss incidents and injuries involving flashover during the month of December. These incidents point to the importance of understanding fire dynamics and reading the fire as part of initial size-up and ongoing dynamic risk assessment. Each member operating on the fireground must maintain a high level of situational awareness and communicate key fire behavior indicators and potential for extreme fire behavior phenomena.

Flashover Disrupts Firefighters’ Rescue Effort

Firefighters attempting to rescue a victim from a burning Portsmouth (VA) house on Thursday were forced to abandon the rescue attempt and exit a window when a flashover occurred.

Firefighters first entered the home through the front door, but were repelled by flames. They then made entrance through the front bedroom windows when the flashover occurred. After escaping, firefighters tried to reenter through the back of the house, but they could not.

FireEngineering.com

Ottawa Firefighter Pulled From Burning Basement

“An Ottawa firefighter had to be rescued from a burning basement after he was caught in a possible flashover yesterday afternoon. We don’t know what happened, and we haven’t had a chance yet to look into exactly what the details were, but we have a feeling that it might have been a flashover,” department spokesman Marc Messier said.

Firehouse.com

Columbus Firefighters Suffer Burns In Flashover

“Flames were coming up from the basement and out of the windows when crews arrived at the Dana Avenue house fire. There was a flashover, and fire crews quickly evacuated the duplex. Two firefighters were injured in the flashover, Battalion Chief David Whiting” said.

Nbc4i.com

Kansas City Firefighters Injured in Flashover

When they arrived, flames were coming from the first and second story of the house, firefighters said.

Kansas City, Mo., Fire Chief Smokey Dyer tells KMBC 9’s Justin Robinson what happened in a fire early Saturday that left three firefighters injured

Kansas City Fire Chief Smokey Dyer said crews went inside and started to go up the stairs, when conditions inside the house suddenly changed. He said it burned the fire hose and left the firefighters completely surrounded by flames. The firefighters sent out a mayday call for help.

In the past 10 years, every significant firefighter injury that we have sustained in fire combat has been a result of a rapid change of conditions,” [emphasis added] Dyer said.

KMBC.com

Incidents such as these point to the need for continued emphasis on developing firefighters’ understanding of practical fire dynamics and effective strategies and tactics to control the fire environment and prevent, rather than react to occurrence of fire phenomena such as flashover.

Flashover is Just Flashover

In a recent discussion with a number of international colleagues, we were challenged to think about language, terminology, and precision when describing fire phenomena. While this is a more obvious challenge when working with firefighters, researchers, and scientists who have different first languages, it is also a day to day problem for firefighters with a common native language (e.g., English).

I have previously raised this question and proposed one approach as a starting point for classification of fire behavior phenomena based on outcome and the conditions required for the phenomena to occur (Language & Understanding: Extreme Fire Behavior and Extreme Fire Behavior: An Organizing Scheme).

Consider two recognized definitions for flashover:

  • Stage of fire transition to a state of total surface involvement in a fire of combustible materials within an enclosure’ (ISO 13943, 2008, 4.156).
  • A transitional phase in the development of a compartment fire in which surfaces exposed to thermal radiation reach ignition temperature more or less simultaneously and fire spreads rapidly throughout the space resulting in full room involvement or total involvement of the compartment or enclosed area (NFPA 921-2007)

This transition is often assumed (and in many cases explicitly stated) to take place between the growth and fully developed stages. However, neither the ISO nor NFPA definition specifies this. In addition, while the NFPA definition indicates that this transition is extremely rapid (i.e., more or less simultaneously), the ISO definition does not describe the speed with which the transition to total surface involvement occurs.

In some respects, flashover is always a transition between the growth and fully developed stage (as increasing heat release rate is necessary). However, this may be a bit misleading. In the modern fire environment a compartment fire may follow an alternate path, often transitioning from growth to decay prior to flashover due to limited ventilation as illustrated in Figure 1.

Figure 1. Fire Development in a Compartment

As illustrated in Figure 1, the traditional fire development curve shows fire progressing neatly through incipient and growth stages, with occurrence of flashover resulting in transition to the fully developed stage and then decay as fuel is consumed.

The path of fire development is often quite different in the modern fire environment. The nature of common building contents provides a rapid increase in heat release rate (HRR) and corresponding oxygen consumption, resulting in the fire becoming ventilation controlled. With heat release limited by ventilation, the fire begins to decay (HRR and temperature are reduced). Uninterrupted this may cause the fire to self-extinguish. However, should an opening be created (as a result of window failure due to fire effects or opening of a door), the fire re-enters the growth stage and transitions through flashover to the fully developed stage. This is sometimes described as ventilation induced flashover (but in some respects, flashover is simply flashover).

In a spirited debate, some of my international colleagues have stated that “all flashover is ventilation induced” as ventilation is necessary to develop sufficient HRR for flashover to occur. Others have said that “flashover is temperature driven” as sufficient upper layer temperature is required. None have specifically said that flashover is a fuel dependent phenomenon, but this is true as well (given that the fuel that is burning must have sufficient energy and heat release rate for flashover to occur). In addition, flashover is dependent on compartment size and configuration, as a given fire will reach flashover in one compartment (generally a smaller one) and not in another). So, what’s the answer? It Depends!

This really boils down to being able to recognize what is important for firefighters to understand about fire development and flashover (as well as other extreme (i.e., extremely rapid changes in) fire behavior.

What We Know and Why It Matters

There are a number of things that we know about compartment fire behavior that are significant when considering how and why flashover occurs:

  • Fire behavior is completely predictable if you have the necessary information and the time to analyze it (but on the fireground you seldom do). Predicting fire behavior is really saying: This is what I think is likely to happen.
  • Changes in the built environment have influenced fire development (but there are a number of variables that may vary from nation to nation). In the US, modern building contents have increased heat of combustion and heat release rate, resulting in more rapid fire development than in the past.
  • If ventilation is adequate, the typical room (e.g., bedroom, living room, family room) has well in excess of the amount of fuel (both in heat of combustion and peak heat release rate) to allow a fire to progress to flashover.
  • Smoke is fuel. This is not dependent on the size or occupancy of the building. Smoke always presents a potential flammability hazard and as the concentration of fuel and energy in the smoke increases (think temperature, even though this is not the same as energy), the hazard increases.
  • When a compartment fire becomes ventilation controlled, pyrolysis continues, adding additional gas phase fuel to the smoke in the upper layer.
  • Building configuration and ventilation profile has a significant impact on fire development. However, despite increased compartment size and open floor plans, fires in modern single family dwellings are likely to be ventilation controlled when the fire department arrives.
  • Increasing the air supplied to a ventilation controlled fire will result in an increased heat release rate (unless you immediately put the fire out) and this can occur quickly. Where you ventilate in relation to the fire, the existing heat release rate, and energy in the upper layer will all influence how quickly these changes occur.
  • Creating an opening for entry is ventilation! This change in the ventilation profile often influences development of ventilation controlled fires by increasing air supply and providing a flow path for fire travel from the current area of involvement to the entry point (watch for a bi-directional air track with air in at the bottom and smoke out at the top of the opening).
  • Adding additional openings will further increase the HRR and speed fire growth (unless you put the fire out). This is true even if the openings are near the seat of the fire.
  • It is unlikely that you can tactically create sufficient ventilation to return a ventilation controlled fire to a fuel controlled burning regime (meaning that as you continue to increase ventilation, HRR will continue to rise). This does not mean that ventilation is bad as you may influence fire spread and the level of the upper layer, but recognize that the fire will get larger (increased HRR).
  • Wind can have a significant influence on fire behavior. Consider wind direction, velocity, and how fire behavior (e.g., HRR, flow path) may change if the ventilation profile changes.

Given what we know, how should this inform our choice of strategies and tactics? Remember that strategies and tactics are context dependent. If you arrive with a single resource and two firefighters, your capabilities are different than if you arrive with six resources and 24 firefighters. Resources change some of your tactical options and the potential for concurrent operations. However, resources and their capability do not change the chemistry and physics of fire dynamics. It is important to recognize potential fire behavior, the scope and magnitude of the problems presented by the incident and the capabilities of the resources at hand.

Recognize that there are no simple answers to the questions of how much risk is too much and what actions are appropriate in a given circumstances. That said the following are steps you can take to reduce the potential of being caught or trapped by rapid fire progress:

  • Recognize the indicators of flashover potential and communicate these observations to the members of your crew. Company officers (crew/team leaders) should communicate observation of flashover indicators to their immediate supervisor (e.g., Command, Division or Group Supervisor).
  • Ensure that fire attack (or any other operation that involves working inside a burning building) and tactical ventilation is coordinated. In more explicit terms this means that ventilation occurs when companies or crews assigned to fire attack can quickly put water on the fire (not when they are ready to call for water or are simply ready to enter the building).
  • Ensure that you are working on a hoseline (or are protected by one) if you are working in a smoke filled environment. Without a charged hoseline you have no defense (you cannot outrun flashover or other rapid fire development phenomena).
  • Take positive actions to reduce the threat. If there are hot gases overhead, cool them. If you can put water directly on the fire, do it. If you put the fire out, things will generally improve! When you can control the fire ventilate to remove the smoke and remove the hazard.
  • Consider the effects of wind on potential fire behavior. Consider exterior attack and avoid advancing lines in the potential flow path when the potential for wind driven fire conditions exits. Use caution when entering from the windward side and control inlet openings (or provide adequate exhaust).

Clearly understand when you are taking a reasonable and calculated risk and when you are gambling. Think about this before you are engaged in a firefight. Make it a conscious decision and not simply a default choice. Field Marshal Erwin Rommel made this distinction between taking risks and gambling: “With a risk, if it doesn’t work, you have the means to recover from it. With a gamble, if it doesn’t work you do not. Normally, to succeed you must take risks. On occasion you have to make a gamble” (Clancy, 1997, p. 152).

What’s Next?

My next post will dig into the findings and tactical implications of the recently released research results and on-line training program from Underwriters Laboratories (UL): Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction.

This training program is of critical importance to anyone fighting fires in today’s buildings. All firefighters and fire officers should complete this training program before the end of January 2011! Take the time and get your head around the implications of this research on what we do on the fireground. This takes a bit of effort as we need to question our assumptions and standard practices, but the outcome is worth the work.

Be a student of our craft, be safe and look out for the firefighters and fire officer that work with you. Have a great New Year!

References

Clancy, T. Into the storm: A study in command. New York: G. F. Putnam & Sons

Lima, Peru: Backdraft

Friday, December 24th, 2010

I recently traveled to Peru to deliver a presentation on 3D Firefighting at the First International Congress on Emergency First Response which was conducted by the Cuerpo General de Bomberos Voluntarios del Perú. This congress was being conducted in conjunction with the Peruvian fire service’s 150th anniversary celebration (establishment of Unión Chalaca No. 1, the first fire company).

In addition to my conference presentation, I spent 10 days teaching fire behavior and working alongside the Bomberos of Lima No.4, San Isidro No. 100, and Salvadora Lima No. 10.

Fire & Rescue Services in Lima, Peru

Lima is a city of 8 million people served by a volunteer fire service which provides fire protection, emergency medical services, hazmat response, and urban search and rescue. The stations that I worked in were busy with call volumes from 2000 to 5000 responses in an urban environment ranging from modern high-rise buildings to poor inner city neighborhoods. Each station was equipped with an engine, truck, rescue, and ambulance. Staffing varied throughout the day with some units being cross staffed or un-staffed due to limited staffing. At other times, units were fully staffed (5-6 on engines and trucks, 4 on rescues, and 3 on ambulances). While the Peruvian fire service has some new apparatus, many apparatus are old and suffer from frequent mechanical breakdown. Faced with high call volume and old apparatus and equipment, the Firefighters and Officers displayed a tremendous commitment to serve their community.

The firefighters I encountered had a tremendous thirst for knowledge and commitment to learning. My friend Giancarlo had arranged for a short presentation on fire behavior for a Tuesday evening and the room was packed. Class was scheduled from 20:00 until 22:00. However, when we reached 22:00, the firefighters wanted to stay and continue class. We adjourned at 24:00. This continued for the next two nights. Sunday, between calls, we had breakfast at San Isidro No. 100 and then conducted a hands-on training session on nozzle techniques and hose handling. At the start of class, Firefighter Adryam Zamora from Santiago Apostol No. 134, related that he used the 3D techniques we had discussed in class at an apartment fire the night before with great success.

Staff Ride

Staff rides began with the Prussian Army in the mid-1800s and are used extensively by the US Army and the US Marine Corps. A staff ride consists of systematic preliminary study of a selected campaign or battle, an extensive visit to the actual sites associated with that campaign, and an opportunity to integrate the lessons derived from these elements. The intent of a staff ride is to put participants in the shoes of the decision makers on a historical incident in order to learn for the future. Wildland firefighters have adapted the staff ride concept and have used it extensively to study large wildland fires, fatalities, and near miss incidents. However, structural firefighters have not as commonly used this approach to learning from the past.

When I traveled to Lima, I only knew two Peruvians; Teniente Brigadier CBP (a rank similar to Battalion Chief in the US fire service) Giancarlo Passalaqua and Teniente CBP (Lieutenant) Daniel Bacigalupo. However, I left Lima with a much larger family with many more brothers and sisters.

Backdraft!

Many firefighters have seen the following video of an extreme fire behavior event that occurred in Lima, Peru. This video clip often creates considerable discussion regarding the type of fire behavior event involved and exactly how this might have occurred. Photos and video of fire behavior are a useful tool in developing your understanding and developing skill in reading the fire. However, they generally provide a limited view of the structure, fire conditions, and incident operations.

Note: While not specified in the narrative, this video is comprised of segments from various points from fairly early in the incident (see Figure 3, to later in the incident immediately before, during, and after the backdraft).

When I was invited to Lima, I asked my friend Teniente Brigadier CBP Giancarlo Passalaqua who worked at this incident, if it would be possible to talk to other firefighters who were there and to walk the ground around the building to gain additional insight into this incident.

The Rest of the Story

The morning after I arrived, I was sitting in the kitchen of San Isidro No. 100 and was joined in a cup of coffee by Oscar Ruiz, a friendly and engaging man in civilian clothing who I assumed was a volunteer firefighter at the station. After my friend Giancarlo arrived, he told me that Oscar was actually Brigadier CBP (Deputy Chief) Oscar Ruiz from Lima No. 4 and one of the two firefighters who had been in the bucket of the Snorkel pictured in the video. Oscar and I had several opportunities to spend time together over the course of my visit and he shared several observations and insights into this incident.

At 11:00 hours on Saturday, March 15, 1997, two engines, a ladder, heavy rescue, medic unit, and command officer from the Lima Fire Department were dispatched to a reported commercial fire at the intersection of Luis Giribaldi Street and 28 de Julio Street in the Victoria section of Lima.

Companies arrived to find a well developed fire on Floor 2 of a 42 m x 59 m (138’ x 194’) three-story, fire resistive commercial building, The structure contained multiple, commercial occupancies on Side A (Luis Giribaldi Street) and Side B (28 De Julio Street). Floors 2 and 3 were used as a warehouse for fabric (not as a plastics factory as reported in the video clip). The building was irregularly shaped with attached exposures on Sides B and C.

Exposure A was a complex of single-story commercial occupancies, Exposure B was an attached two-story commercial complex, Exposure C was an attached three story commercial complex, and Exposure D was a three story apartment building. All of the exposures were of fire resistive construction.

Figure 1. Plot Plan

Floors 2 and 3 had an open floor plan and were used for storage of a large amount of fabric and other materials. As illustrated in Figure 1, there were two means of access to Floors 2 and 3; a stairway on Side A and an open shaft and stairway on Side C.

Due to heavy fire involvement, operations focused on a predominantly defensive strategy to control the fire in this multi-occupancy commercial building. The incident commander called for a second, and then third alarm. Defensive operations involved use of handlines and an aerial ladder working from Side A and in the Side A stairwell leading to Floor 2. However, application of water from the ladder pipe had limited effect (possibly because of the depth of the building and burning contents shielded from direct application from the elevated stream.

Figure 2. Early Defensive Operations

Note: Video screen shot from the intersection of Luis Giribaldi and 28 de Julio.

The third alarm at 14:05 hours brought two engines and articulating boom aerial platform (Snorkel) from Lima 4 to the incident. Snorkel 4, under the command of Captain Roberto Reyna was tasked to replace the aerial ladder which had been operating on Side A and operate an elevated master stream to control the fire on Floor 2 (Figure 2).

Placing their master stream into operation Teniente Oscar Ruiz and Captain Roberto Reyna worked to darken the fire on Floor 2. As exterior streams were having limited effect, Snorkel 4 was ordered to discontinue operation and began to lower the bucket to the ground. At the same time, efforts were underway to gain access to the building from Side C. Using forcible entry tools, firefighters breached the large loading dock door leading to the vertical shaft and stairwell in the C/D quadrant of the building.

Prior to opening the large loading dock door on Side C (Charlie/Delta Corner), a predominantly bi-directional air track is visible at ventilation openings on Side C. Flaming combustion from windows on Side A was likely limited to the area at openings with a bidirectional air track. Combustion at openings on Side A likely consumed the available atmospheric oxygen, maintaining extremely ventilation controlled conditions with a high concentration of gas phase fuel from pyrolyzing synthetic fabrics deeper in the building.

The ventilation profile when Snorkel 4 initially began operations included intake of air through the open interior stairwell (inward air track) serving floors 1-3 and from the lower area of windows which were also serving as exhaust openings (bi-directional air track). Interview of members operating at the incident indicates that there were few if any ventilation openings (inlet or exhaust) on Sides B, C, or D prior to creation of an access opening on Floor 1 Side C.

At approximately 15:50, Snorkel 4 was ordered to stop flowing water. As smoke conditions worsened, they did so and began to lower the aerial tower to the ground. At the same time, crews working to gain access to Floor 1 on Side C, breached the large loading dock door. A strong air track developed, with air rushing in the large opening and up the open vertical shaft leading to the upper floors as illustrated in Figure 3.

Figure 3. Layout of Floors 1 and 2

As the Snorkel was lowered to the ground, Teniente Oscar Ruiz observed a change in smoke conditions, observing a color change from gray/black to “phosphorescent yellow” (yellowish smoke can also be observed in the video clip of this incident). Less than two minutes after the change in ventilation profile, a violent backdraft occurred, producing a large fireball that engulfed Captain Roberto Reyna and Teniente Oscar Ruiz in Snorkel 4 (see Figure 4). The blast seriously injured the crew of Snorkel 4 along with numerous other members from stations Lima 4, Salvadora Lima 10, and Victoria 8 who were located in the Stairwell (these members were blown from the building) and on the exterior of Side A.

This incident eventually progressed to a fifth alarm with 63 companies from 26 of Lima’s 58 stations in attendance.

Figure 4. Backdraft Sequence

Watch the video again; keeping in mind the changes in air track that resulted from breaching the loading dock door on Side C. Consider the B-SAHF (Building, Smoke, Air Track, Heat, and Flame) indicators that are present as the video progresses.

Luis Giribaldi Street and 28 de Julio Street Today

The building involved in this incident is still standing and while it has been renovated, is much the same as it was in 1997. On December 6, 2010, Teniente Brigadier Giancarlo Passalaqua, myself and Capitáin Jordano Martinez went to Luis Giribaldi and 28 de Julio to walk the ground and gain some insight into this significant incident.

Figure 5. Luis Giribaldi Street

As illustrated in Figure 5, Luis Giribaldi Street is a one-way street with parking on both sides and overhead electrical utility lines.

Figure 6. A/D Corner

There are a number of obvious structural changes that have been made since the fire. Including installation of window glazing flush with the surface of the building (the original windows can be seen behind these outer windows).

Figure 7. Snorkel 4’s Position

Figure 7 shows the view from Snorkel 4’s position, just to the left of center is the entry way leading to the stairwell used to access Floors 2 and 3. Piled fabric and other materials can be seen through the windows of Floors 2 and 3, likely similar in nature to conditions at the time of the incident.

Figure 8. Side A

Figure 8 provides a view of Side A and Exposure B, which appears to be of newer construction and having a different roofline than the fire building. The appearance of the left and right sides of the fire building are different, but this is simply due to differences in masonry veneer on the exterior of the building.

Figure 9. A/B Corner

Figure 10. Side B

Figure 11. B/C Corner

As illustrated in Figures 10-11 this block is comprised of several attached, fire resistive buildings. It is difficult to determine the interior layout from the exterior as there are numerous openings in interior walls due to renovations and changes in occupancy over time. The floor plan illustrated in Figure 4 is the best estimate of conditions at the time of the fire based on interviews with members operating at the incident.

Figure 12. Side C and the Loading Dock Door

Figure 12shows Side C of the fire building and Exposure C and the loading dock door that was breached to provide access to the fire building from Side C immediately prior to the backdraft.

Figure 13. Side D and Exposure D

Figure 13illustrates the proximity of Exposure D, a three-story, fire-resistive apartment building.

Lessons Learned

This incident presented a number of challenges including a substantial fuel load (in terms of both mass and heat of combustion), fuel geometry (e.g., piled stock), and configuration (e.g., shielded fire, difficult access form Side C). Analysis of data from the short video clip and discussion of this incident with those involved provides a number of important lessons.

  • Knowledge of the buildings in your response area is critical to safe and effective firefighting operations. While a challenging task, particularly in a large city such as Lima, developing familiarity with common building types and configurations and pre-planning target hazards can provide a significant fireground advantage.
  • Reading the fire is essential to both initial size-up and ongoing assessment of conditions. In this incident, fire behavior indicators may have provided important cues needed to avoid the injuries that resulted from this extreme fire behavior event.
  • Some fire behavior indicators can be observed from one position, while others may not. It is particularly important that individuals in supervisory positions be able to integrate observations from multiple perspectives when anticipating potential changes in fire behavior.
  • Any opening, whether created for tactical ventilation or for entry has the potential to change the ventilation profile. It is important to consider potential changes in fire behavior that may result from changes in ventilation (particularly when the fire is ventilation controlled).
  • Communication and coordination are critical during all fireground operations. It is essential to communicate observations of key fire behavior indicators and changes in conditions to Command. Tactical ventilation (or other tactical operations that may influence fire behavior) must be coordinated with fire attack.
  • Protective clothing and self-contained breathing apparatus are a critical last line of defense when faced with extreme fire behavior (even when engaged in exterior, defensive operations).

I would like to recognize the members of the Peruvian fire service who assisted in my efforts to gather information about this incident and identify the important lessons learned. In particular, I would like to thank Teniente Brigadier Giancarlo Passalaqua, Brigadier CBP Oscar Ruiz, and my brothers at Lima 4 who generously shared their home, their time, and their knowledge.

Ed Hartin, MS, EFO, MIFIreE, CFO

When I was invited to Lima, I asked my friend Teniente Brigadier CBP Giancarlo Passalaqua who worked at this incident, if it would be possible to talk to other firefighters who were there and to walk the ground around the building to gain additional insight into this incident.

UL Ventilation Course

Saturday, December 18th, 2010

Impact of Ventilation on Fire Behavior

Earlier this year, Underwriters Laboratories (UL) conducted a series of full-scale experiments to determine the influence of ventilation on fire behavior in legacy and contemporary residential construction (see Did You Ever Wonder?).

UL University recently releases an on-line training program based on this research. Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction is an excellent examination of the influence of ventilation on fire behavior and discussion of the tactical implications of the lessons learned through this research.

Every Firefighter and Fire Officer should complete
this training program within the next 30 days!

Completion of this on-line program could be the most important 90 minutes of training that you complete in the next year! I do not make this statement lightly. Understanding the relationship between ventilation and fire behavior is a critical competency for firefighters and fire officers.

After completing this on-line training program, consider the following questions and discuss them with the firefighters and fire officers you work with:

  • What are the indicators of a ventilation controlled fire?
  • How do your forcible entry and door entry procedures influence fire behavior?
  • How do you (or do you) coordinate fire attack and ventilation? How can tactical coordination be improved in your department?
  • What hazards are presented when performing VES (Vent, Enter, & Search) under ventilation controlled conditions? How can these hazards be mitigated?
  • What influence do closed doors have on the survivability profile (for either civilian occupants or trapped firefighters)?
  • What other lessons can you draw from this important research?

Research Report

In addition to the on-line course, UL has published a comprehensive report on this important research projects: Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction.

Video

You can also download an excellent video illustrating the difference between fuel characteristics and loading in legacy and contemporary residential occupancies. This video is a tremendous tool to illustrate changes in the built environment to both firefighters and civilian audiences.

High Resolution Video

Low Resolution Video

Lima Backdraft

I am still working the report on my staff ride to the site of the 1997 backdraft at Luis Giribaldi Street and 28 de Julio Street in the Victoria section of Lima, Peru and should have it posted within the next week.

Ed Hartin, MS, EFO, MIFireE, CFO

Homewood, IL LODD: Part 2

Sunday, November 21st, 2010

This post continues examination of the incident that took the life of Firefighter Brian Carey and seriously injured Firefighter Kara Kopas on the evening of March 30, 2010  while they were operating a hoseline in support of primary search in a small, one-story, wood frame dwelling with an attached garage at 17622 Lincoln Avenue in Homewood, Illinois.

This post focuses on firefighting operations, key fire behavior indicators, and firefighter rescue operations implemented after rapid fire progression that trapped Firefighters Carey and Kopas.

Firefighting Operations

After making initial assignments, the Incident Commander performed reconnaissance along Side Bravo to assess fire conditions. Fire conditions at around the time the Incident Commander performed this reconnaissance are illustrated in Figure 7. After completing recon of Side B, the Incident Commander returned to a fixed command position in the cab of E-534 (in order to monitor multiple radio frequencies).

Figure 7. Conditions Viewed from Side C during the Incident Commander’s Recon

Note: John Ratko Photo from NIOSH Death in the Line of Duty Report F2010-10.

Engine 1340 (E-1340) arrived and reported to Command for assignment. The five member crew of this company was split to assist T-1220 with vertical ventilation, horizontally ventilate through windows on Sides B and D, and to protect Exposures D and D2.

One member of E-1340 assisted T-1220 and the remaining members vented the kitchen windows on SidesD and B, while the E-1340 Officer stretched a 1-3/4” (45 mm) hoseline from E-534 to protect exposures on Side D. However, this line was not charged until signficantly later in the incident (see Figure 14). Figure 8 (a-c) illustrates changing conditions as horizontal ventilation is completed on Sides B and D.

Figure 8. Sequence of Changing Conditions Viewed from the A/B Corner

At 2105 Command reported that crews were conducting primary search and were beginning to vent.

Note the B-SAHF indicators visible from the A/B Corner in Figure 8a: Dark gray smoke from the door on Side A with the neutral plane at approximately 18” (0.25 m) above the floor. Velocity and turbulence are moderate and a bidirectional air track is evident at the doorway.

As the 2-1/2” (64 mm) handline reached the kitchen, flames were beginning to breach the openings in the Side C wall of the house and thick black smoke had banked down almost to floor level. As noted in Figure 3 (and subsequent floor plan illustrations), there were doors and windows between the house and addition in the Utility Room and Bedroom 2 . The Firefighter from E-534 had a problem with his protective hood and handed the nozzle off to Firefighter Carey and instructed him to open and close the bail of the nozzle quickly. After doing so, the Firefighter from E-534 retreated along the hoseline to the door on Side A to correct this problem (he is visible in the doorway in Figure 8c).

As E-1340 vents windows on Sides B (see Figure 8b) and D, the level of the neutral plane at the doorway on Side A lifts, but velocity and turbulence of smoke discharge increases. Work continues on establishing a vertical vent, but is hampered by smoke discharge from the door on Side A.

After horizontal ventilation of Sides B and D, velocity and turbulence of smoke discharge continues to increase and level of the upper layer drops to the floor as evidenced by the neutral plane at the door on Side A (see Figures 8b and 8c)

The photo in Figure 8c was taken just prior to the rapid fire progression that trapped Firefighters Carey & Kopas. The Firefighter from E-534 is visible in the doorway correcting a malfunction with his protective hood.

As T-1220B reached the hallway leading to the bedrroms, they felt a significant increase in temperature and visibility worsened. After searching Bedroom 2 and entering Bedroom 1 temperature contiued to increase and T-1220B observed flames rolling through the upper layer in the hallway leading from Bedroom 2 and the Bathroom. Note: NIOSH Death in the Line of Duty Report 2010-10 does not specify if T-1220B searched Bedroom 2, but this would be consistent with a left hand search pattern. They immedidately retreated to the Living Room looking for the hoseline leading to the door on Side A. As they did so, they yelled to the crew on the 2-1/2” (64 mm) handline to get out.

Extreme Fire Behavior

Firefighter Kopas felt a rapid increase in temperature as the upper layer ignited throughout the living room and the fire in this compartment transitioned to a fully developed stage. She yelled to Firefighter Carey, but received no response as she turned to follow the 2-1/2” (64 mm) hoseline back to the door on Side A. She made it to within approximately 4’ (1.2 m) of the front door when her protective clothing began to stick to melted carpet and she became stuck. T-1220B saw that she was trapped, reentered and pulled her out.

Figure 12. Position of the Crews as the Extreme Fire Behavior Phenomena Occurred

Note: It is unknown if T-1220B searched Bedroom 2 before entering Bedroom 1. However, this would be consistent with a left hand search pattern.

Figure 13. Conditions Viewed from the Alpha/Bravo Corner as the Extreme Fire Behavior Occured

Note: Warren Skalski Photo from NIOSH Death in the Line of Duty Report F2010-10.

Figure 14. Conditions Viewed from the Alpha/Delta Corner as the Extreme Fire Behavior Occured

Note: Warren Skalski Photo from NIOSH Death in the Line of Duty Report F2010-10.

Following the transition to fully developed fire conditions in the living room, the Incident Commander ordered T-1220 off the roof. As illustrated in Figure 14, the exposure protection line stretched by E-1340 was not charged until after Firefighter Carey was removed from the building.

Figure 15. Position of Search and Fire Control Crews after Rapid Fire Progress

Firefighter Rescue Operations

The Incident Commander and Firefighter from E-534 (who had retreated to the door due to a problem with his protective hood), pulled a second 1-3/4” (45 mm) line from E-534. T-1220B re-entered the house with this hoseline to locate Firefighter Carey.

While advancing into the living room, T-1220B discovered that E-534’s 2-1/2” (64 mm) handline. They controlled the fire in the living room using a direct attack on burning contents and advanced to the kitchen where they discovered Firefighter Carey entangled in the 2-1/2” (64 mm) handline. Firefighter Carey’s helmet and breathing apparatus facepiece were not in place.

T-1220B removed Firefighter Carey from the building where he received medical care from T-1145. A short time later, Firefighter Carey became apenic and pulseless. After the arrival of Ambulance 2101 (A-2101), Firefighter Carey was transported to Advocate South Suburban Hospital in Hazel Crest, IL where he was declared dead at 10:03 pm.

According to the autopsy report, Firefighter Carey had a carboxyhemoglobin (COHb) of 30% died from carbon monoxide poisoning. The NIOSH Death in the Line of Duty Report (2010) did not indicate if the medical examiner tested for the presence of hydrogen cyanide (HCN) or if thermal injuries were a contributing factor to Firefighter Carey’s death.

Timeline

Review the Homewood, Illinois Timeline (PDF format) to gain perspective of sequence and the relationship between tactical operations and fire behavior.

Contributing Factors

Firefighter injuries often result from a number of causal and contributing factors. NIOSH Report F2010-10 identified the following contributing factors in this incident that led to the death of Firefighter Brian Carey and serious injuries to Firefighter Kara Kopas.

  • Well involved fire with trapped civilian upon arrival.
  • Incomplete 360o situational size-up
  • Inadequate risk-versus-gain analysis
  • Ineffective fire control tactics
  • Failure to recognize, understand, and react to deteriorating conditions
  • Uncoordinated ventilation and its effect on fire behavior
  • Removal of self-contained breathing apparatus (SCBA) facepiece
  • Inadequate command, control, and accountability
  • Insufficient staffing

Questions

The following questions focus on fire behavior, influence of tactical operations, and related factors involved in this incident.

  1. What type of extreme fire behavior phenomena occurred in this incident? Why do you think that this is the case (justify your answer)?
  2. How did the conditions necessary for this extreme fire behavior event develop (address both the fuel and ventilation sides of the equation)?
  3. What fire behavior indicators were present in the eight minutes between arrival of the first units and occurrence of the extreme fire behavior phenomena (organize your answer using Building, Smoke, Air Track, Heat, and Flame (B-SAHF) categories)? In particular, what changes in fire behavior indicators would have provided warning of impending rapid fire progression?
  4. Did any of these indicators point to the potential for extreme fire behavior? If so, how? If not, how could the firefighters and officers operating at this incident have anticipated this potential?
  5. What was the initiating event(s) that lead to the occurrence of the extreme fire behavior that killed Firefighter Carey and injured Firefighter Kopas?
  6. How did building design and construction impact on fire behavior and tactical operations during this incident?
  7. What action could have been taken to reduce the potential for extreme fire behavior and maintain tenable conditions during primary search operations?
  8. How would you change, expand, or refine the list of contributing factors identified by the NIOSH investigators?